REMOTE CONTROL FUNCTIONS
PAGE 18
ENGLISH
ENGLISH
DIP
Switch
Settings
The
PCB
for
the
unit
of
the
Tempo
series
of
single
z
one
mini-splits
has
a
set
of
DIP
switches
that
must
be
set
when
replacing
the
PCB.
The
replacement
PCB
is
shipped
with
all
switches
set
to
the
OFF
position.
S
witch
settings:
SW2-1
Selects
remote
code
A
or
B.
Normally
set
to
the
position
for
code
A
operation.
If
two
units
are
used
in
the
same
area
and
the
user
wishes
to
control
them
separately,
switch
SW2-1of
the
sec
ond
unit
is
set
to
the
ON
position
for
code
B
operation.
T
he
wireless
remote
for
the
second
unit
is
also
set
to
code
B.
SW2-2
Selects
room
card
able
or
disable.
Normally
set
to
the
OFF
position.
Set
to
the
ON
position
when
used
in
conjunction
with
a
room
card
interface
utilized
in ho
tel rooms.
SW-3
&
SW-4
Selects
eeprom
code
22,
25,
33
and
35.
Set
to
identify
the
tonnage
of
the
unit.
Settings:
9K (22) SW
9K (23) SW
9K (23) SW
-3 ON SW-4 ON
-3 OFF SW-4 OFF
-3 OFF SW-4 OFF
-3 OFF SW-4 OFF
12K (25) SW-3 ON SW-4 OFF
12K (26) SW-3 OFF SW-4 ON
12K (26) SW-3 OFF SW-4 ON
12K (26) SW-3 OFF SW-4 ON
12K (26) SW-3 OFF SW-4 ON
12K (26) SW-3 OFF SW-4 ON
18K (33) SW-3 ON
18K (33) SW-3 ON
18K (33) SW-3 ON
18K (33) SW-3 ON
SW
-4 OFF
-4 OFF
24
K
(35) SW-3 ON
24K (35) SW-3 ON
24K (35) SW-3 ON
24K (35) SW-3 ON
SW
-4 ON
-4 ON
DIP Switch
Display Switch Settings
The PCB for the indoor unit of the Tempo series of
zone mini-splits has a set of Display switches that must be set
when replacing the PCB.
Settings:
9K (23) SW
9K (23 ) SW
09K
12K
18K
24K
(387)
(387)
(387)
(387)
J1: ON, J2:ON
J1: ON, J2:ON
J1: ON, J2:OFF
J1: ON, J2:OFF
Switch settings:
If two indoor units use dierent Display, or dierent PCB,
the PCB should switch J1 and J2. J1 set ON, meaning J1 should
be connected, J2 set OFF, meaning J2 should be cut.