EasyManuals Logo
Home>GE>UPS>Digital Energy SG Series

GE Digital Energy SG Series User Manual

GE Digital Energy SG Series
45 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
g
GE
OPM_SGS_ISG_10K_40K_0US_V010.doc 34/45 Installation Guide SG Series 10, 20, 30 & 40 kVA
3.8.7 Battery connection of SG Series 30 and 40 kVA
SGT5000_030-040_UPS connection battery_01US
BATTERY
X3
+
PE
_
Fig. 3.8.7-1 Power connections battery of SG Series 30 and 40 kVA
SG Series 30 and 40 kVA: Max. rating Battery terminals: 1 AWG (50mm
2
)
Battery
+
Positive pole of the Battery
Negative pole of the Battery
Do not insert the Battery Fuses before the commissioning.
Battery cable terminations are to the Positive and Negative Terminals as shown above.
Connect wire to the Terminals using appropriate tools and appropriate torque.
Torque specification for Input / Output and DC power connections on Terminals: See sect.. 3.8.1.
To meet standards concerning electromagnetic compliance, the connection
between the UPS and external battery must be done by using a shielded
cable or suitable shielded (metal) conduit!
This UPS is only designed to operate in a wye-configured electrical system
with a solidly grounded neutral.
If the UPS is equipped with an input transformer for, the secondary of the
transformer must be wye-configured with neutral solidly grounded.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Digital Energy SG Series and is the answer not in the manual?

GE Digital Energy SG Series Specifications

General IconGeneral
BrandGE
ModelDigital Energy SG Series
CategoryUPS
LanguageEnglish

Related product manuals