6.1.1 5/6 kVA PDUs
Model Outlets (NEMA) Inlets (NEMA)
TB 5-20R T L5-20R L5-30R EN60320 L6-20R L6-30R L14-30R TB L14-30P
L1-N-G L2-N-G L1-N-G L2-N-G L1-N-G L2-N-G L1-N-G L2-N-G L1-L2-G L1-L2-G L1-N-L2-G
GT PDU A 01* 1 1
GT PDU A 02 1 1
GT PDU A 03 2 2 1 1 1
GT PDU A 04 1 1 2 1
GT PDU A 05 2 2 2 1
GT PDU A 06 2 2 1
GT PDU A 07 2 2 1 1 1
GT PDU A 08 2 2 2 1
GT PDU A 09 4 1
*: No 3 pole 6 ms maximum transfer time manual bypass
6.1.2 8/10 kVA PDUs
Outlets (NEMA)
Model 5-20R T-type L5-20R L6-20R L6-30R
L1-N-G L2-N-G L1-N-G L2-N-G L1-L2-G L1-L2-G
GT PDU B 01 4 4 2
GT PDU B 02 2 2 4
GT PDU B 03 2 2 4
GT PDU B 04 2 2 2 2
GT PDU B 05 2 2 1 1 2
GT PDU B 06 2 2 4
6.2 EXTENDED RUNTIME
Extended runtime can be obtained by connecting a separate battery extension pack to the UPS. In this
case the UPS must be informed about the new total battery capacity to allow a reliable recalculation of
the available runtime (via UPS monitoring software). Depending of the charge condition of the new
batteries the new runtime calculations may temporarily be unreliable.
Additional batteries increase the recharging time for the unit; all other operational information is the same
as for standard models. The following table shows runtimes with up to 3 Battery Packs. 1 Battery Pack is
the normal configuration.
Unit Load Internal Batteries 1 Battery Pack 2 Battery Pack 3 Battery Pack
10% 75 min 156 min 235 min 313 min
25% 31 min 75 min 115 min 155 min
50% 14 min 34 min 58 min 82 min
75% 8 min 22 min 35 min 50 min
GT5000 RT
100% 5 min 14 min 25 min 36 min
10% 75 min 156 min 235 min 313 min
25% 31 min 75 min 115 min 155 min
50% 14 min 34 min 58 min 82 min
75% 8 min 22 min 35 min 50 min
GT6000 RT
100% 5 min 14 min 25 min 36 min
10% 107 min 251 min 333 min 494 min
25% 40 min 100 min 160 min 225 min
50% 16 min 39 min 66 min 92 min
75% 10 min 24 min 41 min 58 min
GT8000 RT
100% 6 min 17 min 28 min 41 min
10% 107 min 251 min 333 min 494 min
25% 40 min 100 min 160 min 225 min
50% 16 min 39 min 66 min 92 min
75% 10 min 24 min 41 min 58 min
GT10000 RT
100% 6 min 17 min 28 min 41 min
modifications reserved 34 User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)