9 SPECIFICATIONS
Model : GT5000 GT6000 GT8000 GT10000
Ratings
Power ratings depending on input voltage : VA / W VA / W VA / W VA / W
100V / 200V : 4000 / 3400 4800 / 3400 6400 / 6400 8000 / 6400
110V / 220V : 4500 / 3800 5400 / 3800 7200 / 7200 9000 / 7200
115V / 230V : 5000 / 4000 6000 / 4200 8000 / 8000 10000 / 8000
120V / 208V : 4800 / 4200 5200 / 4200 8000 / 6900 8700 / 8000
120V / 240V : 5000 / 4200 6000 / 4200 8000 / 8000 10000 / 8000
127V / 220V : 4800 / 4200 5200 / 4200 8000 / 6900 8700 / 8000
Input thermal circuit breaker (A) : 30 30 60 60
Internal input fuse 250V, slow (A) : 30 30 30*2 30*2
Input converter
AC input voltage : Nominal: 120 / 208 V
AC input voltage range : 100/(173-200), 110/(190-220), 115/(198-230), 120/(208-240), 127/(220) V
Input current waveform : sine wave
Input current (A) at nominal input voltage : 20 20 40 40
Input power factor : > 0.97
Input frequency range : 40 - 70 Hz
Input phase (L1 to L2) : 120° / 180° / 240° ±10°
Inrush current : 40 40 40 40
Output converter
AC output voltage : 100 / 110 / 115 / 120 / 127 V (selectable)
AC output voltage tolerance : L-N ± 3%; L1-L2 ± 5% L-N ± 2%; L1-L2 ± 5%
Output frequency : 50 / 60 Hz, auto selection
Output frequency range : nominal ± 5% with mains synchronizing
Output waveform : sine wave
Harmonic distortion : < 3% with linear load, < 5% with non-linear full load
Power factor at nominal input voltage : 0.87 0.8 0.86 0.92
Crest factor (peak to RMS current) : 3 : 1
Capacity appliance outlets : with 55A Terminal Block
Bypass
AC input voltage range : ± 15% of selected output voltage
Frequency tracking rate : 1Hz/s
Frequency tracking range : ± 5% of selected frequency
Typical transfer time, msec : 0
Overload capability : fully protected against overload and short circuits
Overload behavior during battery operation : 130% during 10 seconds 130% during 1 minute
: 200% during 2 seconds 200% during 5 seconds
Overload behavior during bypass operation : depends on rating of thermal circuit breaker overload protection
125% of TCB value for 200 seconds 110% for 300 seconds
200% of TCB value for 10 seconds 130% for 30 seconds
300% of TCB value for 4 seconds 200% for 5 seconds
Batteries (ratings given for 25ºC)
Nominal voltage (Vdc) : 144 144 288 288
Number / Ah batteries
(in battery kit and battery ext. pack) : 12pcs / 8Ah 12pcs / 8Ah 24pcs / 8Ah 24pcs / 8Ah
Type : REW45-12 FR
Service life : up to 5 years (depending on use)
Recharge current : 1 A
Battery recharge time
(batt. discharged at 100% load) : 6 hours for 90% capacity 3 hours for 90% capacity
Runtime in minutes
at typical load (75%) : 8 8 9 9
25% : 31 31 40 40
50% : 14 14 16 16
75% : 8 8 9 9
100% : 5 5 5 5
General
Weight UPS kg : 30.3 Kg (67 lbs) 49.3 Kg (109 lbs)
Dimensions UPS (h
xwxd) : 176x430x592 mm (6.9x16.9x22.55 in) 267x430x660 mm (10.5x16.9x26 in)
Weight battery pack kg : 43 Kg (94.7 lbs) 91 Kg (200.4 lbs)
Dimensions battery pack : 87x430x592 mm (3.47x16.9x2255 in) 173x430x660 mm (6.8x16.9x26 in)
Enclosure / protection : steel-plastic / IP20
Environment
Safety : UL1778
Electromagnetic compatibility : EMI: FCC CFR47 Part 15, class A, ESD: IEC61000-4-2, level 4
RS: IEC61000-4-3, level 3, EFT: IEC61000-4-4, level 4, Surge: IEC61000-4-5, level 3
ANSI C62.41 (IEEE587) Category A (level 3) & B (level 1)
Ambient temperature : 0 to +40ºC
Audible noise at 1 meter : < 55 dB(A), load and temperature dependent
Max. relative humidity : 90% (non-condensing)
Color : Black - RAL 9005
modifications reserved 41 User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)