LX: OPM_MAE_XXX_2K2_3K0_XGB_V020 9 GE DE Match 2200-3000: user manual 2.0 (GB)
GE Digital Energy
g
Whenever a malfunction occurs, first check external factors (e.g connections, temperature, humidity or
load) to determine whether the problem is caused by the unit itself or by its environment. Subsequently
check the thermal circuit breaker: it may be tripped. If so: reset it (see 4, fig.1) and be sure that the UPS is
not overloaded.
The following chart is a simple troubleshooting checklist only; if the suggested solution does not succeed,
or if the information is insufficient to solve the problem, please contact your dealer or consult
www.gedigitalenergy.com.
PROBLEM POSSIBLE CAUSE SOLUTION
Connected equipment not
operating properly, buzzer sounds
continuously
Overload causes reduced output
voltage
Reduce load
UPS overload
Reduce load, reset TCB
(4, fig. 1)
Thermal Circuit Breaker (TCB)
tripped
System failure Please contact your dealer or
consult www.gedigitalenergy.com
UPS will not switch on to normal
operation, LED 'on' remains off
(charger off)
Line cord not connected Read 2.2 'Installation'
Connect line cord
Dead socket-outlet, or mains
voltage < approx. 187Vac, or mains
frequency out of tolerance
Contact qualified electrician.
Battery start is possible: see 3.1.2
UPS overtemperature Read 2.1
Allow UPS to cool down
TCB tripped See above
UPS will not switch on to normal
operation, LED 'on' blinks
Mains voltage between 140-
187Vac
Contact qualified electrician
Batteries depleted Allow the UPS to recharge the
batteries
Battery pack not connected Read 2.2 ‘Installation’
Connect battery pack
UPS will not switch to battery
operation
System failure Please contact your dealer or
consult www. gedigitalenergy.com
Shut down by external (software)
command during mains failure
Wait until mains returns
UPS overtemperature Read 2.1
Allow UPS to cool down
Mains failure, battery discharged Wait until mains returns
Programmed shutdown in progress See 3.3.9
UPS switched off automatically
The load is < 5% of the max. load
and no mains power is present.
(No-load shutdown function is
active, see 3.2.3)
Wait until mains returns
LED ‘replace battery’ illuminates,
buzzer is silent
Battery Test just after installation or
mains failure
Allow the UPS to recharge the
batteries
Battery Test shows weak battery Read 6.2, have the batteries
replaced
7 - Troubleshooting

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Match and is the answer not in the manual?

GE Match Specifications

2200

Power IconPower
voltage amperes2200 VA
watts with resistive load1540 W
ac input voltage220 - 240 V
maximum ac input voltage350 V
minimum start-up ac voltage187 V
input frequency50 Hz or 60 Hz
input frequency rangenominal ± 5 Hz
no-load power consumption15 W
max. ac input current12 A
ac input tcb16 A
ac output voltage230 V
output frequency50Hz or 60Hz
output frequency stability< ± 0.1Hz
power factor0.7
Battery IconBattery
nominal voltage36 Vdc
number x capacity of batteries6x7 Ah
recharge current3.5 - 10 A
battery recharge time for 90% capacity2 hours
runtime at typical load (75%)7 minutes
Operating Environment IconOperating Environment
ambient temperature at std. runtime-10 to +40°C
sound at 1 meter< 35 dB(A)
maximum relative humidity95% (non-condensing)
Weight and Dimensions IconWeight and Dimensions
weight of ups18.0 kg
weight of battery pack21.3 kg
dimensions (hxwxd)225 x 185 x 485 mm

3000

Power IconPower
voltage amperes3000 VA
watts with resistive load2100 W
ac input voltage220 - 240 V
maximum ac input voltage350 V
minimum start-up ac voltage187 V
input frequency50 Hz or 60 Hz
input frequency rangenominal ± 5 Hz
no-load power consumption15 W
max. ac input current16 A
ac input tcb16 A
ac output voltage230 V
output frequency50Hz or 60Hz
output frequency stability< ± 0.1Hz
power factor0.7
Battery IconBattery
nominal voltage48 Vdc
number x capacity of batteries8x7 Ah
recharge current3.5 - 10 A
battery recharge time for 90% capacity2 hours
runtime at typical load (75%)7 minutes
Operating Environment IconOperating Environment
ambient temperature at std. runtime-10 to +40°C
sound at 1 meter< 35 dB(A)
maximum relative humidity95% (non-condensing)
Weight and Dimensions IconWeight and Dimensions
weight of ups20.1 kg
weight of battery pack26.5 kg
dimensions (hxwxd)225 x 185 x 485 mm