LX: OPM_MAE_XXX_2K2_3K0_XGB_V020 8 GE DE Match 2200-3000: user manual 2.0 (GB)
GE Digital Energy
g
Apart from the options described in 4.2 and 4.3 the following options are possible:
5.1 Extended Runtime
Extended runtime can be obtained by connecting more than one battery pack to the UPS (see 2.2.1). In
this case, to allow a reliable recalculation of the available runtime, the UPS must be informed about the
new total battery capacity. You can reprogram the battery capacity through the RS232 port, using the UPS
configuration tool that came with the unit (CD ROM, see 6.3). Simultaneously the recharge current will be
increased. Please note that if the UPS is not connected to the mains, and the battery pack is
disconnected from the UPS, the unit will return to the default settings.
Dependent of the charge condition of the new batteries the new runtime calculations may temporarily be
unreliable.
For extended runtime at 25
°
C ambient temperature no derating is required. For extended runtime at 35
°
C,
maximum load must be derated to 1.85kVA (Match 2200) and 2.5kVA (Match 3000).
5.2 PowerFLAG SerVICe Box for Modem Connection
If you connect the PowerFLAG SerVICe Box between the communication port of the UPS and a modem,
a programmed number can be dialed in case of a UPS alarm. It also allows service personnel to dial in
and check the status of the UPS to perform remote diagnostics. This way service costs, specially in
remote areas, can be reduced considerably.
6.1 General
The GE Digital Energy Match UPS is virtually maintenance free: take care of proper environmental
conditions and keep air inlets-outlets free of dust.
Please read 2.1.
6.2 Batteries
The service life of the battery is up to 6 years, depending on operating conditions.
As a healthy battery is critical to the performance of the UPS, an automatic battery test is performed
regularly to ensure failsafe operation. Moreover, keypad 'I' allows a manually started battery test.
See 3.2.4.
When the condition of the battery is critical, a
'replace battery'
alarm will be activated. Have your dealer
replace the batteries as soon as possible. See 3.3.6.
6.3 UPS Configuration Tool
With the UPS configuration software, that came with the unit on CD ROM, you are able to change the
setting of the 'auto-off' function (3.2.3) and reprogram the battery capacity (5.1).
Insert the CD ROM in your computer, and
1. Select RUN from the start menu
2. Type a:\conftool (type for 'a' the appropriate drive letter)
3. Press ENTER
See also a:\README.TXT.
5 - Optional Features
6 - Maintenance

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Match and is the answer not in the manual?

GE Match Specifications

2200

Power IconPower
voltage amperes2200 VA
watts with resistive load1540 W
ac input voltage220 - 240 V
maximum ac input voltage350 V
minimum start-up ac voltage187 V
input frequency50 Hz or 60 Hz
input frequency rangenominal ± 5 Hz
no-load power consumption15 W
max. ac input current12 A
ac input tcb16 A
ac output voltage230 V
output frequency50Hz or 60Hz
output frequency stability< ± 0.1Hz
power factor0.7
Battery IconBattery
nominal voltage36 Vdc
number x capacity of batteries6x7 Ah
recharge current3.5 - 10 A
battery recharge time for 90% capacity2 hours
runtime at typical load (75%)7 minutes
Operating Environment IconOperating Environment
ambient temperature at std. runtime-10 to +40°C
sound at 1 meter< 35 dB(A)
maximum relative humidity95% (non-condensing)
Weight and Dimensions IconWeight and Dimensions
weight of ups18.0 kg
weight of battery pack21.3 kg
dimensions (hxwxd)225 x 185 x 485 mm

3000

Power IconPower
voltage amperes3000 VA
watts with resistive load2100 W
ac input voltage220 - 240 V
maximum ac input voltage350 V
minimum start-up ac voltage187 V
input frequency50 Hz or 60 Hz
input frequency rangenominal ± 5 Hz
no-load power consumption15 W
max. ac input current16 A
ac input tcb16 A
ac output voltage230 V
output frequency50Hz or 60Hz
output frequency stability< ± 0.1Hz
power factor0.7
Battery IconBattery
nominal voltage48 Vdc
number x capacity of batteries8x7 Ah
recharge current3.5 - 10 A
battery recharge time for 90% capacity2 hours
runtime at typical load (75%)7 minutes
Operating Environment IconOperating Environment
ambient temperature at std. runtime-10 to +40°C
sound at 1 meter< 35 dB(A)
maximum relative humidity95% (non-condensing)
Weight and Dimensions IconWeight and Dimensions
weight of ups20.1 kg
weight of battery pack26.5 kg
dimensions (hxwxd)225 x 185 x 485 mm