EasyManua.ls Logo

GE Match - Technical Specifications; Ratings and Input;Output; Battery and Runtime

GE Match
11 pages
Print Icon
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LX: OPM_MAE_XXX_2K2_3K0_XGB_V020 10 GE DE Match 2200-3000: user manual 2.0 (GB)
GE Digital Energy
g
Match model : 2200 3000
Ratings at std. runtime
Voltage Amperes (VA), : 2200 3000
with computer type load
Watts (W) : 1540 2100
with resistive load
For ratings with extended runtime see 5.1
Input
AC input voltage : 220 - 240 V
AC input voltage window : 140 - 305 V, mains operation (if I
in
< 16A)
Maximum AC input voltage : 350V (above 305V battery operation)
Minimum start-up AC voltage : 187 V (at any load)
Input frequency : 50 Hz or 60 Hz
Input frequency range : nominal ± 5 Hz
No-load power consumption,
normal operation : typically 15W
Max. AC input current (A) : 12 16
AC input TCB (A) : 16 16
Output
AC output voltage : 230 V (suitable for 220 - 240 V loads)
AC output voltage tolerance : nominal ± 2% (battery operation, RMS value)
Output frequency : 50Hz or 60Hz (autosensing)
Output frequency in case
of battery start : last detected frequency (off factory 50 Hz)
Output frequency stability : < ± 0.1Hz (battery operation)
Output waveform : sine wave
Power factor : 0.7
Transfer time : typical 4 ms.
Buck/Boost voltage regulation : at 140-305 V input voltage: output voltage 190-254V
Batteries (ratings given for 25°C)
Nominal voltage (Vdc) : 36 48
Number x capacity (Ah) of batteries : 6x7 8x7
Type : 12V, sealed lead acid, maintenance free
Service life : up to 6 years (depending on use)
Recharge current : 3.5 - 10A, depending on programmed battery capacity
Battery recharge time for 90%
capacity (hours, approximation) : 2 2
Runtime in minutes
at typical load (75%) : 7 7
Watts
60 210 263
180 82 104
300 50 69
420 35 47
600 22 30
900 11 17
1540 5 7
2100 - 5
General
Weight of UPS (kg) : 18.0 20.1
Weight of battery pack (kg) : 21.3 26.5
Dimensions (hxwxd, mm)
UPS and battery pack : 225 x 185 x 485
Enclosure / protection : steel - plastic / IP20
Environment
Safety : EN 50091-1-1
Electromagnetic compatibility : EN 50091-2
Ambient temperature at std. runtime : -10 to +40°C;
Sound at 1 meter : < 35 dB(A)
Maximum relative humidity : 95% (non-condensing)
8 - Specifications