3.3. Parameter function description
Fn_00 Factory adjustment parameter. Do not change.
Fn_01 : Accelerate time = 0.1 up to 999 sec
Fn_02 : Decelerate time = 0.1 up to 999 sec
1. Accelerate/decelerate time calculation formula:
Setting Frequency Accelerate time = Fn_01 x
60 Hz
Setting Frequency Decelerate time = Fn_02 x
60Hz
Fn_03 : Operation mode selection =
0 : Forward / Stop , Reverse / Stop
1 : Run / Stop , Forward / Reverse
Note 1: Fn_03 take effect only when Fn_10 = 1 (external operation control)
(1) Reverse command is ignored when Fn_22 = 1
Fn_03 = 0
control method
Fn_03 = 1
control method
3 FWD /Stop
4 REV /Stop
3 Run / Stop
4
FWD/ REV
5 COM
5 COM
TM2 PIN3
TM2 PIN4
Fn_03=0
Output
Forward
Forward
Reverse
(1)
Reverse
(1)
Fn_03=1
Output