Power Fault ALARMS (SSR_SHORT, NO_VOLTAGE e NO_CURRENT)
44
dg.t
R/W
Refresh SSR SHORT
The alarm activates after 3 seconds.
1...999 sec
10
45
dg.f
R/W
Time lter for NO_VOLTAGE, SSR_OPEN and NO_CURRENT alarms
Note: set a value not less than cycle time.
0...99 sec
10
43
hd.2
R/W
Enable POWER_FAULT alarms
0
Table of Power Fault alarms
Reading state
7
bit
State of alarmSSR_
SHORT
R
8
bit
State of alarm
NO_VOLTAGE
R
9
bit
State of alarm
NO_CURRENT
R
12
bit
Reset SSR_SHORT
/ NO_VOLTAGE / NO_
CURRENT/HB alarms
OFF= -
ON= reset alarms
R/W
114
R
State of alarms ALSTATE IRQ
0
0
Table State of alarms
0 ... 1
115
R Status 2
0
Table Status 2
Table Status 3
Overheat alarm
The controller has a temperature sensor for the internal heatsink.
The temperature value of the heatsink is in variable IN_NTC; the over_heat alarm trips when the temperature
exceeds 105°C.
This condition may be caused by obstructed air vents or by a blocked cooling fan.
With the over_heat alarm on, the control disables control output SSR.
There is another maximum temperature protection that disables the hardware for the SSR control.
101
R IN_NTC: SSR temperature °C
102
R
DER_NTC: temperature derivative
of the SSR
°C / 12sec
Reading state
117
R Status 3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran GTF and is the answer not in the manual?

gefran GTF Specifications

General IconGeneral
Brandgefran
ModelGTF
CategoryController
LanguageEnglish

Related product manuals