HW/SW INFORMATION
122
UPD
R
Software version code
120
R Manufacturer - Trade Mark (Gefran) Name of manufacturer 5000
121
R Device ID (GTFP) Product ID 213
Read state
55
R/W Current state (STATUS_W) Table settings STATUS_W
0
bit
0 AL.HB or Power Fault
1 AL.HB
2 Power Fault
3 AL.SSR short
4 No Voltage
5 No Current
6 Fuse_open or Load_short_protection
13 ON/OFF
14 AUTO/MAN
bit
3 Select ON/OFF
4 Select AUTO/MAN
129
R
State saved in eeprom
(STATUS_W_EEP)
115
R Status2 Table status2
117
R Status3 Table status3
The following data registers can be used to identify the controller HW/SW and check its operation.
bit
0 SSR temperature sensor broken
1 SSR over heat
2 phase_softstart_active
3 phase_softstart_end
4 frequency_warning_or monophase_missing_line_warning
5 60Hz
6 short_circuit_current phase softstart
7 Peak current limiter phase softstart
8 RMS current limiter system
9 rotation_error (only for slave biphase conguration)
10 LINE-LOAD Terminals over heat (GTF 150...250A)
11 -
12 Over Peak HSC current limiter phase softstart
13 Current Transformer sensor broken