.47..46.
9. Troubleshooting9. Troubleshooting
The inverter is designed in accordance with the most important international grid-tied
standards and safety and electromagnetic compatibility requirements. Before delivering to
the customer, the inverter has been subjected to several tests to ensure its optimal operation
and reliability.
In case of failure, the LCD screen will display an alarm message. In this case, the inverter
may stop feeding into the grid. The failure descriptions and their corresponding alarm
messages are listed in Table 9.1:
Alarm Message
OV-G-V01/02/03/04
OV-G-F01/02
UN-G-F01/02
G-IMP
NO-GRID
OV-DC01/02/03/04
OV-BUS
UN-BUS01/02
GRID-INTF01/02
Failure description
Over grid voltage
Under grid voltage
Over grid frequency
Under grid frequency
High grid impedance
No grid voltage
Over DC voltage
Over DC bus voltage
Under DC bus voltage
Grid interference
Solution
1.Resistant of AC cable is too high.
Change bigger size grid cable
2.Adjust the protection limit if it’s
allowed by electrical company.
1.Check connections and grid switch.
2.Check the grid voltage inside inverter
terminal.
1.Reduce the module number in series
1.Restart inverter
2.Change power board
1.Check PV input connections
2.Check DC input voltage
(single phase >120V, three phase >350V)
3.Check if PV+/- is reversed
Inverter no power
on LCD
No power
LCD show initializing
all the time
Can not start-up
1.Check if the connector on main
board or power board are fixed.
2.Check if the DSP connector to
power board are fixed.
1.Use user define function to adjust the
protection limit if it’s allowed by
electrical company.
1.Check inverter inductor connection
2.Check driver connection
UN-G-V01/02
DC-INTF
DC input overcurrent
1.Restart inverter
2.Identify and remove the string to the fault MPPT
2.Change power board
IGFOL-F
Grid current tracking fail
OV-G-I
Over grid current
OV-DCA-I
IGBT-OV-I Over IGBT current
1.Restart inverter or contact installer.
IG-AD
Grid current sampling fail
INI-FAULT
Initialization system fault
1.Restart inverter or contact installer.
12Power-FAULT
12V power supply fault
DSP-B-FAULT
Comm. failure between main
and slave DSP
Alarm Message
Failure description
Solution
1.Remove all DC input, reconnect and
restart inverter one by one.
2.Identify which string cause the fault and
check the isolation of the string.
PV ISO-PRO
01/02
PV isolation protection
OV-TEM
Over Temperature
1.Check inverter surrounding ventilation.
2.Check if there’s sunshine direct on
inverter in hot weather.
DCinj-FAULT High DC injection current
1.Check AC and DC connection
2.Check inverter inside cable connection.
1.Restart inverter or contact installer.
ILeak-PRO
01/02/03/04
Leakage current protection
RelayChk-FAIL
Relay check fail
AFCI self-detection
(model with AFCI
module)
AFCI module self-detect fault
1.Restart inverter or connect technician.
Arcing protection
(model with AFCI
module)
Detect arc in DC circuit
1. Check inverter connection whether arc
exists and restart inverter.
Screen OFF
with DC applied
Inverter internally damaged
1. Do not turn off the DC switches as it will
damage the inverter.
2. Please wait for the solar irradiance reduces
and confirm the string current is less than
0.5A with a clip-on ammeter and then turn
off the DC switches.
3. Please note that any damages due to wrong
operations are not covered in the device
warranty.
Table 9.1 Fault message and description
NOTE:
If the inverter displays any alarm message as listed in Table 9.1; please
turn off the inverter (refer to Section 6.2 to stop your inverter) and wait for 5
minutes before restarting it (refer to Section 6.1 to start your inverter). If the
failure persists, please contact your local distributor or the service center.
Please keep ready with you the following information before contacting us.
1. Serial number of Solis Three Phase Inverter;
2. The distributor/dealer of Solis Three Phase Inverter (if available);
3. Installation date.
4. The description of problem (i.e. the alarm message displayed on the LCD and the status
of the LED status indicator lights. Other readings obtained from the Information submenu
(refer to Section 6.2) will also be helpful.);
5. The PV array configuration (e.g. number of panels, capacity of panels, number of strings
, etc.);