[page 8] | gpelectric.com
(304mm)
12”
(51mm)
2”
(124mm)
4.9”
(124mm)
4.9”
(346mm)
13.6”
(7mm) (13mm)
.28”
(321mm)
12.6”
.51”
(205mm)
8.1”
(349mm)
13.7”
(378mm)
14.9”
REMOTE
BATTERY
TEMP
ON/OFF
STATUS
INV. / CHR.
MODE
AC INPUT
INV. AC
OUTPUT
NEG
-
POS
+
BATTERY
TEMP
REMOTE
CAUTION:
• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE
COMPARTMENT. OVERHEATING MAY RESULT. • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. • TO REDUCE RISK OF
ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY. • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL
RESULT. • PROVIDED WITH INTEGRAL PROTECTION AGAINST OVERLOADS. • CHARGE ONLY LEAD ACID TYPE
RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.
MISE EN GARDE:
POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE
PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT. RISQUE DE SURCHAUFFE. •
RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE
D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ. • POUR RÉDUIRE LES
RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION. • L’ORIENTATION
DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT. • FOURNI AVEC UNE
PROTECTION INTÉGRALE CONTRE LA SURCHARGE. • NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES
CONTENANT CHACUNE 6 ou 12 CELLULES.
WARNING:
THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO PREVENT FIRE OR
EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS. • RISK
OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT
BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER
TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT. • RISK OF ELECTRIC SHOCK,
HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING. • INTENDED FOR CONTINUOUS DUTY.
AVERTISSEMENT:
• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES
ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT
DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES. • RISQUE DE
DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA
MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE
PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT
CONNECTÉS À CE PRODUIT. • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE,
TESTER AVANT DE TOUCHER. • PRÉVU POUR UNE UTILISATION CONTINUE.
DANGER:
TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION
- PROTECTED EQUIPMENT IS REQUIRED.
• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT
MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ
CB2
INPUT
50A
CB1
INPUT
50A
REMOTE
BATTERY
TEMP
ON/OFF
STATUS
INV. / CHR.
MODE
AC INPUT
INV. AC
OUTPUT
NEG
-
POS
+
CAUTION:
• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE
COMPARTMENT. OVERHEATING MAY RESULT. • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. • TO REDUCE RISK OF
ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY. • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL
RESULT. • PROVIDED WITH INTEGRAL PROTECTION AGAINST OVERLOADS. • CHARGE ONLY LEAD ACID TYPE
RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.
MISE EN GARDE:
POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE
PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT. RISQUE DE SURCHAUFFE. •
RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE
D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ. • POUR RÉDUIRE LES
RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION. • L’ORIENTATION
DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT. • FOURNI AVEC UNE
PROTECTION INTÉGRALE CONTRE LA SURCHARGE. • NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES
CONTENANT CHACUNE 6 ou 12 CELLULES.
WARNING:
THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO PREVENT FIRE OR
EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS. • RISK
OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT
BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER
TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT. • RISK OF ELECTRIC SHOCK,
HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING. • INTENDED FOR CONTINUOUS DUTY.
AVERTISSEMENT:
• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES
ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT
DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES. • RISQUE DE
DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA
MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI
AVEC CE
PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT
CONNECTÉS À CE PRODUIT. • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE,
TESTER AVANT DE TOUCHER. • PRÉVU POUR UNE UTILISATION CONTINUE.
DANGER:
TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION
- PROTECTED EQUIPMENT IS REQUIRED.
• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT
MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ
CB2
INPUT
50A
CB1
INPUT
50A
CAUTION:
• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE
COMPARTMENT. OVERHEATING MAY RESULT. • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. • TO REDUCE RISK OF
ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY. • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL
RESULT. • PROVIDED WITH INTEGRAL PROTECTION AGAINST OVERLOADS. • CHARGE ONLY LEAD ACID TYPE
RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.
MISE EN GARDE:
POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE
PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT. RISQUE DE SURCHAUFFE. •
RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE
D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ. • POUR RÉDUIRE LES
RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION. • L’ORIENTATION
DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT. • FOURNI AVEC UNE
PROTECTION INTÉGRALE CONTRE LA SURCHARGE. • NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES
CONTENANT CHACUNE 6 ou 12 CELLULES.
WARNING:
THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO PREVENT FIRE OR
EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS. • RISK
OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT
BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER
TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT. • RISK OF ELECTRIC SHOCK,
HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING. • INTENDED FOR CONTINUOUS DUTY.
AVERTISSEMENT:
• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES
ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT
DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES. • RISQUE DE
DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA
MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE
PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT
CONNECTÉS À CE PRODUIT. • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE,
TESTER AVANT DE TOUCHER. • PRÉVU POUR UNE UTILISATION CONTINUE.
DANGER:
TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION
- PROTECTED EQUIPMENT IS REQUIRED.
• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT
MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ
CB2
INPUT
50A
CB1
INPUT
50A
Temperature Sensor
®
®
MODEL: GP-IC2000-12 Inverter / Charger
gpelectric.com
Inverter Operation
Continuous Output Power (-20~40°C): 2000VA DC Input: 12.6V
Maximum Continuous Input Current: 267ADC Nominal AC Output Voltage/Frequency: 120VAC(±5%)/60Hz(±0.1Hz)
Maximum Continuous Output Current: 16.7AAC Surge Power: 3400 Real Watts (5 seconds) THD: <5%
Charger Operation
Bypass Operation
Continuous Charger Current (-20~40°C) : 100 ADC@14.4 VDC nominal with 120 VAC / 60Hz (15 AAC) input
Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC
Input Voltage: 120 VAC
Maximum AC Input Current: 50 AAC
Maximum Power: 12000 VA
DC Output Range: 8.5 to 16.5VDC
Grid Input Frequency: 60Hz
Generator Input Frequency Range: 50 to 70Hz
Power Factor: >0.98
Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.)
Certified to CSA C22.2 No. 107.1-01
5GW2
MQ7275
MARINE POWER INVERTER
5DA7
E198012
POWER INVERTER
E483757
®
MODEL: GP-IC2000-12 Inverter / Charger
gpelectric.com
Inverter Operation
Continuous Output Power (-20~40°C): 2000VA DC Input: 12.6V
Maximum Continuous Input Current: 267ADC Nominal AC Output Voltage/Frequency: 120VAC(±5%)/60Hz(±0.1Hz)
Maximum Continuous Output Current: 16.7AAC Surge Power: 3400 Real Watts (5 seconds) THD: <5%
Charger Operation
Bypass Operation
Continuous Charger Current (-20~40°C) : 100 ADC@14.4 VDC nominal with 120 VAC / 60Hz (15 AAC) input
Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC
Input Voltage: 120 VAC
Maximum AC Input Current: 50 AAC
Maximum Power: 12000 VA
DC Output Range: 8.5 to 16.5VDC
Grid Input Frequency: 60Hz
Generator Input Frequency Range: 50 to 70Hz
Power Factor: >0.98
Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.)
Certified to CSA C22.2 No. 107.1-01
5GW2
MQ7275
MARINE POWER INVERTER
5DA7
E198012
POWER INVERTER
E483757
®
MODEL: GP-IC2000-12 Inverter / Charger
gpelectric.com
Inverter Operation
Continuous Output Power (-20~40°C): 2000VA DC Input: 12.6V
Maximum Continuous Input Current: 267ADC Nominal AC Output Voltage/Frequency: 120VAC(±5%)/60Hz(±0.1Hz)
Maximum Continuous Output Current: 16.7AAC Surge Power: 3400 Real Watts (5 seconds) THD: <5%
Charger Operation
Bypass Operation
Continuous Charger Current (-20~40°C) : 100 ADC@14.4 VDC nominal with 120 VAC / 60Hz (15 AAC) input
Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC
Input Voltage: 120 VAC
Maximum AC Input Current: 50 AAC
Maximum Power: 12000 VA
DC Output Range: 8.5 to 16.5VDC
Grid Input Frequency: 60Hz
Generator Input Frequency Range: 50 to 70Hz
Power Factor: >0.98
Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.)
Certified to CSA C22.2 No. 107.1-01
5GW2
MQ7275
MARINE POWER INVERTER
5DA7
E198012
POWER INVERTER
E483757
4
9
1
1
9
8
7
6
5
4
3
2
7
8
2
DC Ground
Terminal
AC Entry/Exit
Terminals
Status LED
Positive (+)
DC Terminal
Intake Air
Vents (and on
right side)
Negative (-)
DC Terminal
Mounting
Flange
Power
ON/OFF Switch
Dip
Switches
Remote Control
Port
Battery Sensor
Port
Inverter/Charger
Mode
6
5
11
10
1112 10
3
GENERAL INFORMATION
2.4 UNIT FEATURES
AC Entry/Exit Terminals - Two 1-3/8” knockouts provided to accommodate up to 1-1/4” 50 amp RV Cable. Strain relief
clamps provided to secure the AC input and output wires.
DC Ground Terminal - Use this connection to ground the exposed chassis of the inverter to the DC grounding system.
This terminal accepts CU/AL conductors from #14 to #2 AWG (2.1 to 33.6mm
2
).
Remote Control Port - Use this port to connect the optional remote control unit to the Inverter/Charger.
Battery Temperature Sensor Port - Use this port to connect the battery temperature sensor to the Inverter/Charger.
Mounting Flange - Use this to secure the Inverter/Charger to the mounting surface.
Negative (-) DC Terminal - Use this connection point to secure the battery bank negative (-) cable to the Inverter/Charger.
Always ensure the DC terminal cover is used to protect this terminal.
Positive (+) DC Terminal - Use this connection point to secure the battery bank positive (+) cable to the Inverter/Charger.
Always ensure the DC terminal cover is used to protect this terminal.
Intake Air Vents - These cut-outs are used as ventilation openings. Air is drawn in through the front of the Inverter/Charger
and passes through to keep the electronics cool for optimum performance.
Status LED - Green, Red Blink, Red Fast Blink, Orange Solid, Orange Blink & Orange Fast Blink Status. See page 38 for
further explanation.
Inverter/Charger LED - Inverter Mode = Solid Green
Charging Mode = Green Blink
Power ON/OFF Switch - Thispushbuttonswitchcanbeusedtoturntheuniton/o󰀨.Warning!PowerOFFdoesnotdis-
connect the batteries or AC power source. Therefore, the “AC output load” is still active.