Note:
The requirement of RS485 communication cable: standard RS485 cable.
3. The choice of 120 ohm termination resistor dip switch (DT series only).
• If there is single DT series inverter, RS485 connection cable with waterproof terminal can
realize the connection
• For single inverter communication, choose one among the two terminals. Please use a
waterproof cover to cover the port which is not used.
• 120 ohms termination resistor is controlled by dip switch. "ON" means connected, and "OFF"
means disconnected.
• For single inverter communication, put on the dip switch near the terminal (default is OFF).
Then shielding layer of communication cable is single point grounding.
• If there are several PV inverters, their connection can be realized by RS485 communication
cables in a daisy chain connection.
• For the last inverter in the daisy chain, put on the dip switch near the terminal (default is OFF).
Then shielding layer of communication cable is single point groundin.
120Ω Termination Resistor Dip Switch
4. RS485 communication method
• DT series inverter can be connected with EzLogger pro separately for data acquisition and
monitoring.
• The connection method of single DT inverters, EzLogger pro and PC terminal.
120Ω Termination
Resistor Dip Switch
Inverter
RS485-OUT
EzLogger Pro
Internet
Router
Ethernet
PC
RS485 Cable
Earthing of shield
RS485-IN
120Ω
1. The connection steps of RS485 communication of DT/SDT series inverter are as follows:
Step 1: Screw this plate off from inverter.
Step 2:
Put the cable through the plate, and connect
RS485 cable on the 4-pin terminal.
Advise to use cable 16AWG-26AWG.
123456
The
Insulator
Screw Cap
RS485
communication board Cable
Single hole
seal ring
NutLock
No.
1
2
3
4
5
6
Function
RS485+
RS485-
Reserved
Reserved
RS485+
RS485-
Step 3:
Connect the terminal to the right position onto the inverter and screw the plate.
CT/METER
DRED
RS485
RS485
RS485
RS485
RS485
AC OUTPUT
RS485
CT/METER
DRED
DT
SDT
6.5mm
25mm
2. Connect the inverter to EzLogger Pro with RS485 cable, and EzLogger Pro to switch or router
with CAT5E STP cable.