D Series Modular Air-cooled Scroll Chillers
40
Overload
protection
The voltage is too high or too low
The discharge pressrue is too high or too
low
The backwater temperature is too high
The overloaded elment malfunctions
The ambient temperateure is too high
The motor and wiring terminal is short-
circuited
Check the voltage which is required to
be within the rated value ±20V and the
exceedance of the phase di󰀨erence to be
within ±30%
Check the discharge pressure and gure out
why
Check the backwater temperature and gure
out why
Check the electric current of the compressor
Improve the ventilation
Check the corresponding resistance of the
motor and the terminal
Internal over-
temperature
protection
The voltage is too high or too low
The discharge pressure is too high
The entering chilled water temperature is
too high
The internal overtemperature protection
device malfunctions
Refrigerant is charged insu󰀩ciently
Check the voltage which is required to be
within the allowable range
Check the discharge pressure and gure out
why
Check the entering chilled water and gure
out why
Take the leakage test
Low pressure
protection
The check valve or the drier-lter is
clogged
The expanson valve malfunctions
The low pressure switch malfunctions
Refrigerant is charged insu󰀩ciently
Replace the check valve or the drier-lter
Adjust or replace the expansion valve
Check the low presure switch
Add refrigerant
Failure to
startup
The circuit breaker trips or the fuse is
blown out
The control circuit fails to get through
There is no electric currrent
High or low pressure protection acts
The contact coil is blown out.
Power phase is wired improperly
The water system malfunctions and the
ow switch is opened
An alarm is raised on the wired controller
The ON/OFF Timer is improperly set
The temperature sensor is set out of the
set point
Replace the damaged element
Check the wiring of the control system
Check the power supply
See “Too high discharge pressure”, “Too low
discharge pressure”, “Too high discharge
pressure”, and “Too low discharge pressure”
Replace the damaged element
Rewire the power phase
Check the water system
Check the alarm type and take
countermeasures
Check and adjust the set point
WARNING
Without commissioning, warranty will turned invalid under the following conditions:
Refrigerant leaks in that the user personally opens some valve or pipe connector.
The user personally dismantles the unit without Gree’s approval.
The user personally powers the control cabinet or the compressor motor.
The user personally charges oil or refrigerant to the unit.
The user personally starts up the system.
The user personally passes directly hot water or steam to the evaporator.
The user fails to operate the unit following the instructions covered in this manual.
8.2 After-sales Service
When the unit in warranty has a quality issue or fails to operate properly under the allowable operation
condition, please contact the local sales representative for free service.
The user is required to designate personnel to take charge of the unit following the instructions covered
in this manual, otherwise any maintenance cost caused by the improper operation will be at the user’s
expense.