EasyManuals Logo
Home>Gree>Air Conditioner>GTH36K3FI

Gree GTH36K3FI User Manual

Gree GTH36K3FI
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
U-Match Series DC Inverter Service Manual
14
Note: Nominal capacities are based on the follow conditions.
Mode
Indoor
Outdoor
Cooling
DB:27(80.6)
WB:19(66.2)
DB:35(95)
WB:24(75.2)
Heating
DB:20(68)
WB:--(--)
DB:7(44.6)
WB:6(42.8)
Piping
Length
09k-42k
5m
48k-60k
7.5m
The air volume is measured at the relevant standard external static pressure.
Noise is tested in the semianechoic room, so it should be slightly higher in the actual operation due
to environmental change.
3.2 Operation Range
Mode
Range of Outdoor Temperature
Cooling
-15-48
Heating
-10-24
3.3 Electrical Data
3.3.1 Outdoor unit
Table 1-4-1 Electrical Data of Outdoor Unit
Model
Compressor
Fan Motor
Fuse
Capacity
Breaker
Capacity
Min. Power
Supply Cord
Power Supply
Qty.
RLA
FLA
V/Ph/Hz
A
A
A
A
mm
2
GUHD09NK3FO
220-240,1,50
1
4.5
<1
3.15/5
10
1.0
GUHD12NK3FO
1
4.5
<1
3.15/5
10
1.0
GUHD18NK3FO
1
7.2
<1
5/15
16
1.5
GUHD24NK3FO
1
11.5
<1
5/30
20
2.5
GUHD30NK3FO
1
11.5
<1
5/30
20
2.5
GUHD36NK3FO
1
19
<1
5/30
32
4.0
GUHD42NK3FO
1
19
<1
5/30
32
4.0
GUHD48NK3FO
1
21
<1
3.15/5
40
6.0
GUHD36NM3FO
380-415,3,50
1
8
<1
5
16
1.5
GUHD42NM3FO
1
8
<1
5
16
1.5
GUHD48NM3FO
1
8
<1
5
16
1.5
GUHD60NM3FO
1
8
<1
5
16
1.5

Table of Contents