6.2 Brief Description of Modes and Functions
●
Indoor Unit
●
Indoor Unit
1Temperature Parameters
ƹ
Indoor preset temperature (Tpreset)
Indoor ambient temperature (Tamb.)
s (The temperature in this manual is expressed by Centigrade. If Fahrenheit is used, the switchover between them is
Tf=TcX1.8+32.)
Once the compressor is energized, there should be a minimum in
terval of 3 minutes between two start-ups. But if the unit is
de-energized and then energized, the compressor can restart
2.1.1 Cooling conditions and process
When
Tamb. ≥Tpreset, the unit starts cooling operation. In this case, the compressor and the outdoor fan operate and the indoor fan
operates at set speed.
When Tamb. ≤Tpreset-3
ć, the compressor and the outdoor fan stop while the indoor fan runs at set speed.
3ć˘Tamb. ˘Tpreset, the unit will maintain its previous running status.
In cooling mode, temperature setting range is 1
630ć; the indoor unit displays operation icon, cooling icon and set temperature.
When outdoor unit has malfunction or stops for protection, indoor unit will keep previous operation status and display malfunction
code.
2.1.3 The protection status is as the same as the cooling mode.
2.3 Heating mode (not available for cooling only
2.3.1 Heating conditions and process
When
Tamb. ≤Tpreset+2ć, the unit starts heating operation. In this case, compressor and outdoor fan operate simultaneously; the
indoor fan operates at cold-air prevention mode.
ć, the compressor and outdoor fan stop operation; the indoor fan blows residual heat.
preset
+2ć˘T
amb.
˘ T
preset
+5ć, the unit will maintain its previous running status.
Under this mode, temperature setting range is 16
; the indoor unit displays operation icon, heating icon and set temperature.
Tpreset
Tpreset –3 ˚C
Compressor
Outdoor fan
Indoor fan
Run
Tamb.
Stop
Stop cooling
Start cooling
Previous running status
≥ 6 min. ≥ 3 min. ≥ 6 min.
Set fan speed
When Tamb.>Tpreset, the unit operates in cooling mode. Meanwhile, compressor and outdoor fan operate, and indoor fan operates a
set fan speed (low fan speed, quiet fan speed or auto quiet fan speed).When Tpreset-2
℃<Tamb. ≤Tpreset, the unit keeps previous
operation status.When Tamb. ≤Tpreset-2
℃, compressor, outdoor fan and indoor fan operate at set fan speed (low fan speed, quiet fan
speed or auto quiet fan speed).Under this mode, the temperature setting range is 1
. Display displays operation icon, drying icon
and set temperature.
Tpreset
Tpreset –2˚C
Compressor
Outdoor fan
Indoor fan
Run
Tamb.
Stop
Stop cooling
Start cooling
Previous running status
≥ 6 min. ≥ 3 min. ≥ 6 min.
Set fan speed