Air-to-water Heat Pump
26
MONOBLOC
TYPE
How to Wire Thermostat
(1) Uncover the front cover of indoor unit and open the control box;
(2) Identify the power specication of the thermostat, if it is 230V, nd terminal block XT5 as NO.22~24 and
block XT6 as NO.33~34;Otherwise, if it is 24V, nd terminal block XT5 as NO.17~21;
(3) If it is the heating/cooling thermostat, please connect wire as per the gure above.
NOTE
Note
• 220V power supply can be provided to the thermostat by the Versati III heat pump.
• Setting temperature by the thermostat(heating or cooling) should be within the temperature range of the product ;
• For other constrains, please refer to previous pages about the remote air temperature sensor;
• Do not connect external electric loads. Wire 220V AC should be used only for the electric thermostat;
• Never connect external electric loads such as valves, fan coil units, etc. If connected, the mainboard of the unit can be
seriously damaged;
• Installation of the thermostat is very similar to that of the remote air temperature sensor.
10. 2-Way Valve
The role of 2-way valve 1 is to control the water ow into the underoor loop. When “Floor Cong” is set to “With”
for either cooling or heating operation, it will keep open. When “Floor Cong” is set to “ Without”, it will keep closed.
General Information
Type Power Operating Mode Supported
NO 2-wire 230V 50Hz ~AC
Closing water ow Yes
Opening water ow Yes
NC 2-wire 230V 50Hz ~AC
Closing water ow Yes
Opening water ow Yes
(1) Normal Open type. When electric power is NOT supplied, the valve is open. (When electric power is
supplied, the valve is closed.)
(2) Normal Closed type. When electric power is NOT supplied, the valve is closed. (When electric power is
supplied, the valve is open.)
(3) How to Wire 2-Way Valve:
Follow steps below to wire the 2-way valve.
Step 1. Uncover the front cover of the unit and open the control box.
Step 2. Find the terminal block and connect wires as below.
3 4 5
2-Way Valve 1
N OV alv e
N
3 4 5
2-Way Valve 1
NC Valv e
N
3 4 5
2-Way Valve 1
L 1(OFF )
L2(ON)
N
WARNING
ote
• Normal Open type should be connected to wire (OFF) and wire (N) for valve closing in cooling mode.
• Normal Closed type should be connected to wire (ON) and wire (N) for valve closing in cooling mode.
(ON) : Line signal (for Normal Open type) from PCB to 2-way valve
(OFF) : Line signal (for Normal Closed type) from PCB to 2-way valve
(N) : Neutral signal from PCB to 2-way valve
11. 3-Way Valve