EasyManuals Logo
Home>Gree>Heat Pump>Versati III

Gree Versati III User Manual

Gree Versati III
180 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
Air-to-water Heat Pump
30
MONOBLOC
TYPE
switch on (outdoor)temperature and control logic(1/2).
14. Gate-controller
If there is gate control function, installation guide follow as:
220-240VAC
15. Charging and Discharging of Refrigerant
The unit has been charged with refrigerant before delivery. Overcharging or undercharging will cause the
compressor to run improperly or be damaged. When refrigerant is required to be charged or discharged for
installation, maintenance and other reasons, please follow steps below and nominal charged volume on the
nameplate.
Discharging: remove metal sheets of the outer casing, connect a hose to the charging valve and then discharge
refrigerant.
Charging
valve 1
Charging
valve 2
Notes
(a) Discharge is allowed unless the unit has been stopped. (Cut off the power and repower it 1 minutes later)
(b) Protective measures should be taken during discharging to avoid frost bites.
(c) When discharging is nished, if vacuuming cannot be done immediately, remove the hose to avoid air or
foreign matters entering the unit.
(d) Vacuuming: when discharging is finished, use hoses to connect the charging valve, manometer and
vacuum pump to vacuum the unit.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree Versati III and is the answer not in the manual?

Gree Versati III Specifications

General IconGeneral
BrandGree
ModelVersati III
CategoryHeat Pump
LanguageEnglish

Related product manuals