9
Oponal third limit (extended open posion)
The third limit is a handy opon for high doors that rarely need to be fully opened. The third limit is a door posion above the open limit
posion which can be accessed when needed. Having this upper stopping posion allows a mid height limit to be set as a rst opening
point, while a further press of the open buon takes the door to a higher set posion.
Seng the third limit
Once the Open and Closed limits have been set:
1. Posion the door at the open limit posion
2. While holding the UP buon, press the SET buon 3 mes.
The LIMIT ERROR indicator will ash
3. Now open the door further unl the door is in the desired extended open posion
4. Press SET to save this as the extended open posion.
The LIMIT ERROR indicator will quickly ash then go out
Accessing the third limit:
1. Open door to rst upper limit
2. Press the UP buon
OPERATION
Seng limits using the SBF eDrive+2.0
Unl the three limits required for the SBF to be operaonal have been set, the Call For Service light will ash connually.
Ensure a Normally Closed signal or link wire is connected to the Fire Trip Input (see the SBF manual for further details)
1. While holding STOP, press the SET buon 3 mes.
The Limit ERROR indicator will start ashing signifying ‘limit seng mode’
2. Use the DOWN buon to drive the door to the desired CLOSED posion.
The manual hand chain can be used to accurately posion the door before pressing SET
3. Press the SET buon to save this as the CLOSED posion.
The LIMIT ERROR indicator will ash quickly then return ashing slowly
4. Use the UP buon to drive the door to the desired SMOKE BAFFLE posion. This must be at or above 2100mm from ground level
The manual hand chain can be used to accurately posion the door before pressing set
5. Press SET again to save this as the SMOKE BAFFLE posion.
The LIMIT ERROR indicator will ash quickly then will go out
5. Posion the door at the SMOKE BAFFLE posion
6. While holding the UP buon, press the SET buon 3 mes
The LIMIT ERROR indicator will ash
8. Use the UP buon to drive the door to the desired OPEN posion.
The manual hand chain can be used to accurately posion the door before pressing set
9. Press SET again to save this as the OPENED posion.
The LIMIT ERROR indicator will ash quickly then will go out
The Closed, SMOKE BAFFLE and Open limits have now been set. If at anyme you need to exit ‘limit seng mode’, just press the STOP
buon.
Once set, operate the door between limits 2 – 3 mes to check they are suitable. If not, return to STEP 1.
OPERATION