Harman® • PF-120 Installation Manual_R1 • 2014 -___ • 03/1413
3-90-08121i
36”
12”
16”
28”
28”
18-1/8” 18-1/8”
16”
Figure 4.6
Chimneystallerthan20’abovetheconnectionwillrequirea
drafttesttodetermineifthedraftistoohigh.
Note:TheHighBurnDraftshouldnotexceed.85IWC.Some
formofarestrictorplatemayberequiredatthetopofhigh
chimneystoreducethedraft.SeeSectionC“Draft”fortest
proceduresandreadings.
Figure 4.4
See “Requirements
for Terminating
the Venting” On
previous page
36”
12”
Figure 4.7
Figure 4.5
The shaded area is where the clearance for the PLvent
pipemustbemaintainedat3”.Aftertheventingleavesthe
shadedareaitmaybeinstalledaspertheventmanufacturer
instructions.(Onlylisted4”pelletventwallpass-throughsand
restopsmaybeused.)SeeFigures4.4&4.6.
Creosote - Formation and Need for Removal -Whenwoodisburnedslowly,itproducestarandotherorganicvapors,
whichcombinewithexpelledmoisturetoformcreosote.Thecreosotevaporscondenseintherelativelycoolchimneyue
ofaslow-burningre.Asaresult,creosoteresidueaccumulatesontheuelining.Whenignited,thiscreosotemakesan
extremelyhotre.Thepelletventpipeshouldbeinspectedatleasttwicemonthlyduringtheheatingseasontodetermine
ifacreosotebuilduphasoccurred.Ifcreosotehasaccumulateditshouldberemovedtoreducetheriskofachimneyre.
Guidanceonminimizingcreosoteformationandtheneedforperiodiccreosoteremoval:Thechimneyshouldbeinspected
duringtheheatingseasontodetermineifacreosotebuild-uphasoccurred.Ifasignicantlayerofcreosotehasaccumulated
(3mmormore)itshouldberemovedtoreducetheriskofachimneyre.
This furnace may be used and installed into an existing
masonryorClassAmetalchimney.
Certain Canadian and Local Codes may require that the
chimney be fully relined. See Figure 4.5.
This Furnace May Notbeventedintoachimneyueserving
anotherappliance.
The chimney should be cleaned and or inspected before
installation.