Harman® • PF-120 Installation Manual_R1 • 2014 -___ • 03/1420
3-90-08121i
B. Blower Assembly
Installtheblowermountingbracketsontheblowerasshown
inFigure5.8.
1. Install(4)TekscrewsoneachsidewhereshowninFigure
5.8.Startwiththetwocenterscrews.
NOTE:Therearetwosmallholesinthedischargeendofthe
blowerthatmatchthetwocenterholesonthesmallangle
oftheblowerbracket.Thetwo(2)outerholesaredrilledby
theTekscrews.
2. Mountblowerwithbracketsinstalledonthefurnaceas
showninFigure5.9.Eachsidewillrequire6Tekscrews.
MountingScrews
NOTE: These Blower Motors are not designed to be
operated without any positive static back pressure.
OPERATION WITHOUT SUPPLY DUCT WORK OR IN
FREE AIR WILL CAUSE MOTOR OVERLOAD AND
PREMATURE FAILURE.
3. Mountthelterboxonthefurnacewith(6)#10x3/4Tek
screws,3oneachsideFigure5.10.Visuallylocatethese
holessoyouarefamiliarwiththeirlocationonthelter
boxandthefurnace.Accesstothemountingholescan
begainedthroughthebloweraccesspanelcoverandthe
lteropening.Figure5.11.
Note: Twopiecesof2x4stackedlayingatontheoor12
inches from the blower opening will support the lter box
duringinstallation
Figure 5.8
Figure 5.9
Figure 5.10
Figure 5.11
Regardless of the supply air duct size installed, the
DistributionBlowerMotorMUSTbecheckedforrunning
Amperage. Check the motor name plate for the full
loadAMPS.Iftheamperageisrunninghigherthanthat
listed,asupplyairrestrictingdampermayberequired
toincreasethesupplyplenumpositivestaticpressure.