X-CPU 01 4 Start-up
HI 801 009 E Rev. 4.00 Page 35 of 52
Routings
The Routings tab contains the routing table. This table is empty if the module is new. A
maximum of 8 routing entries are possible.
Designation Description
Name Denomination of the routing settings
IP Address
Target IP address of the communication partner (with direct host routing)
or network address (with subnet routing).
Range of values: 0.0.0.0 ... 255.255.255.255
Default value: 0.0.0.0
Subnet Mask Define the target address range for a routing entry.
255.255.255.255 (with direct host routing) or subnet mask of the
addressed subnet.
Range of values: 0.0.0.0 ... 255.255.255.255
Default value: 255.255.255.255
Gateway IP address of the gateway to the addressed network.
Range of values: 0.0.0.0 ... 255.255.255.255
Default value: 0.0.0.1
Table 19: Routing Parameters
Ethernet Switch
Designation Description
Port
Port number as printed on the housing; per port, only one configuration
may exist.
Range of values: 1...4
Speed
[Mbit/s]
10 Mbit/s: Data rate 10 Mbit/s
100 Mbit/s: Data rate 100 Mbit/s
1000 Mbit/s: Data rate 1000 Mbit/s (processor module)
Autoneg (10/100/1000): Automatic baud rate setting
Default value: Autoneg
Flow Control Full duplex: Simultaneous communication in both directions
Half duplex: Communication in one direction
Autoneg: Automatic communication control
Default value: Autoneg
Autoneg also
with Fixed
Values
The Advertising function (forwarding the speed and flow control properties)
is also performed if the parameters Speed and Flow Control have fixed
values.
This allows other devices with ports set to Autoneg to recognize the HIMax
port settings.
Limit Limit the inbound multicast and/or broadcast packets.
Off: No limitation
Broadcast: Limit broadcast packets (128 kbit/s)
Multicast and Broadcast: Limit multicast and broadcast packets (1024
kbit/s)
Default value: Broadcast
Table 20: Ethernet Switch Parameters