SJ200 Inverter
Operations
and Monitoring
4–53
Analog Output Operation
In inverter applications it is useful to monitor
the inverter operation from a remote location or
from the front panel of an inverter enclosure. In
some cases, this requires only a panel-mounted
volt meter. In other cases, a controller such as a
PLC may provide the inverter’s frequency
command, and require inverter feedback data
(such as output frequency or output current) to
confirm actual operation. The analog output
terminal [AM] serves these purposes.
The inverter provides an analog voltage output on terminal [AM] with terminal [L] as
analog GND reference. The [AM] can output inverter frequency or current output value.
Note that the voltage range is 0 to +10V (positive-going only), regardless of forward or
reverse motor rotation. Use C028 to configure terminal [FM] as indicated below.
The [AM] signal offset and gain are adjustable, as indicated below.
The graph to the right shows the effect of the
gain setting. To calibrate the [AM] output for
your application, follow the steps below:
1. Verify that the inverter is in Stop Mode.
2. Use C086 to adjust the offset voltage. The
factory default (0V) is the correct value for
most cases. Otherwise, you can have a
positive voltage at zero speed or current.
3. Run the motor at the full scale speed.
a. If [AM] represents output frequency, use
B080 to set the voltage for full scale
output (up to 10V).
b. If [AM] represents motor current, use B080 to set the voltage for full scale
output. Remember to leave room at the upper end of the range for increased
current when the motor is under heavier loads.
Func. Code Description Range
C028
00 Output frequency 0 – Max. frequency (Hz)
01 Output current 0 – 200%
Func. Description Range Default
B080 [AM] analog signal gain 0 to 255 100
C086 [AM] terminal offset tuning 0 – 10V 0.0
A GND
Analog
Voltage Output
12 11LH O
OI AM
CM2
See I/O specs on page 4–6.
+
10VDC
full scale,
1mA max
[AM]
Hz
or
A
0
1/2 full
scale
Full
scale
output
B080=200%
B080=100%
B080=50%
10V
5V

Table of Contents

Other manuals for Hitachi SJ200 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi SJ200 Series and is the answer not in the manual?

Hitachi SJ200 Series Specifications

General IconGeneral
BrandHitachi
ModelSJ200 Series
CategoryInverter
LanguageEnglish

Related product manuals