EasyManuals Logo
Home>Hitachi>Inverter>SJ200 Series

Hitachi SJ200 Series User Manual

Hitachi SJ200 Series
276 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #58 background imageLoading...
Page #58 background image
Step-by-Step Basic Installation
Inverter Mounting
and Installation
2–20
Please use the terminal arrangement below corresponding to your inverter model.
NOTE: An inverter powered by a portable power generator may receive a distorted
power waveform, overheating the generator. In general, the generator capacity should be
five times that of the inverter (kVA).
CAUTION: Be sure that the input voltage matches the inverter specifications:
• Single/Three phase 200 to 240 V 50/60 Hz (up to 2.2kW) for NFEF/NFU models
• Three phase 200 to 240V 50/60Hz (above 2.2kW) for LFU models
• Three phase 380 to 480 V 50/60Hz for HFEF models
CAUTION: Be sure not to power a three-phase-only inverter with single phase power.
Otherwise, there is the possibility of damage to the inverter and the danger of fire.
Inverter models SJ200–002NFEF/NFU to –005NFEF/NFU
Inverter models SJ200–007NFEF to –022NFEF,
–007NFU to –037LFU, –004HFEF/HFU to –040HFEF/HFU
Jumper
Jumper
Chassis
Ground
Chassis
Ground
RB
U/T1
RB
U
/T1
V
/T2
W
/T3
Inverter models SJ200–055HFEF/HFU, –075HFEF/HFU
Jumper
U/T1
V/T2
W/T3
Chassis
Ground
+1 +
L1 L2
+1 +
L1 L2 N/L3
L1 L2 L3
NFEF, NFU
LFU, HFEF, HFU
L3
+1 +
RB
L1 L2
V/T2
W/T3
N/L3
U/T1
V/T2
W/T3

Table of Contents

Other manuals for Hitachi SJ200 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi SJ200 Series and is the answer not in the manual?

Hitachi SJ200 Series Specifications

General IconGeneral
BrandHitachi
ModelSJ200 Series
CategoryInverter
LanguageEnglish

Related product manuals