Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is EET.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display or
controller (Fig. 2).
6. Check / Set operating parameters - see list
7. Save values - if changed
8. Log the controller on to the network then verify
settings on Genus InTouch panel, Set-up Unit
or DIN Box Display.
Fault Finding:
Set-up Unit does not reach the first
screen.
• If the red LED beside the display connector is
ON, then the controller is faulty.
You cannot log the controller on to the
network.
• There may be a controller with the same name,
already logged on the network.
• There may be a maximum 32 controllers
already on the network segment.
• Check on the InTouch panel, P.C. or
Parameter DIN Range/Units Default
HT(LT)
Dsgn Act.
Cut in Temperature 0 -49 to 30 / °C 0 (-20)
Differential Below 1 0 to 30 / °C 1.5 (2)
Air On / Off Weight 2 0 to 100 / % 50
OT Alarm 4 -49 to 60 / °C 5 (-16)
UT Alarm 3 -49 to 60 / °C -2 (-25)
Alarm Delay 5 00:00 to 99:00/Min:Sec 20:00
Defrost Start 6 00:00 to 23:59/Hrs:Mins 01:00
Number of Defrosts per Day 7 0 to 8 6
No Defrost Time 8 0 to 25 / Hrs. 7
Gas Defrost Detect 9 0 to 30 / °C 18
Defrost Terminate Temperature 10 -49 to 30 / °C 10 (14)
Defrost Minimum Time 11 00:00 to 99:00/Min:Sec 05:00
Defrost Maximum Time 12 00:00 to 99:00/Min:Sec 24:00
(25:00)
Drain Down Time 13 00:00 to 20:00/Min:Sec 01:30
Defrost Recovery Time 14 00:00 to 99:00/Min:Sec 30:00
Defrost Type: 0=Elect.; 1= 2Gas
; 2= 3Gas
15 0 to 2 0
Defrost Mode: 0=Local ;
1=Remote
16 0 to 1 0
Defrost Hold: 0=Off ; 1=On 17 0 to 1 0
Fans in Defrost: 0=Off ; 1=On 18 0 to 1 1
Hour 19 0 to 23
Minute 20 0 to 59
Day 21 0 to 31
Month 22 0 to 12
Year 23 0 to 99
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On
24 0 to 2 0
Lights / Blind: 0=Local ;
1=Remote ; 2=Man.Off ;
3=Man.On
25 0 to 3 0
Sunday:Lights(Blinds) On (Up) 26 00:00 to 23:59/Hrs:Mins 08:00
Sunday:Lights(Blinds) Off(Down) 27 00:00 to 23:59/Hrs:Mins 20:00
Monday: On(Up) 28 00:00 to 23:59/Hrs:Mins 08:00
Monday: Off(Down) 29 00:00 to 23:59/Hrs:Mins 20:00
Tuesday: On(Up) 30 00:00 to 23:59/Hrs:Mins 08:00
Tuesday: Off(Down) 31 00:00 to 23:59/Hrs:Mins 20:00
Wednesday: On(Up) 32 00:00 to 23:59/Hrs:Mins 08:00
Wednesday: Off(Down) 33 00:00 to 23:59/Hrs:Mins 20:00
Thursday: On(Up) 34 00:00 to 23:59/Hrs:Mins 08:00
Thursday: Off(Down) 35 00:00 to 23:59/Hrs:Mins 20:00
Friday: On(Up) 36 00:00 to 23:59/Hrs:Mins 08:00
Friday: Off(Down) 37 00:00 to 23:59/Hrs:Mins 20:00
Saturday: On(Up) 38 00:00 to 23:59/Hrs:Mins 08:00
Saturday: Off(Down) 39 00:00 to 23:59/Hrs:Mins 20:00
Superheat reference 40 8.0 (6.0)
Proportional Gain 41 2.0
Integral Gain 42 Do not change the 2.0
Integral Time 43 value of these 03:00
EEV Size 44 parameters 1.0
Temp. Proportional Gain 45 1.5
Temp. Integral Gain 46 0.7
Temp. Integral Time 47 10:00
Manual Defrost: 0=Off ; 1=On 99 0 to 1 0
Display Alarm Messages:
AL Temperature alarm
Ft Probes 1 and 2 are faulty
Pn probe ‘n’ faulty or not connected
(Where ‘n’ = probe number)
EE EEPROM fault
rr Internal program fault
En Plant fault (‘n’ = number)
Store:..................................................
Controller
Name:
Designer:.............................................
Date:...................................................
Engineer:.............................................
Date:...................................................
Comments:
Universal Controller - F/G Door
ZA-10066-EET
Issue a : 14/5/97