Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is
EET.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display
or controller (Fig. 2).
6. Check / Set operating parameters - see
list
7. Save values - if changed
8. Log the controller on to the network then
verify settings on Genus InTouch panel,
Set-up Unit or DIN Box Display.
Fault Finding:
Set-up Unit does not reach the first
screen.
If the red LED beside the display
connector is ON, then the controller is
faulty.
You cannot log the controller on to
the network.
There may be a controller with the same
name, already logged on the network.
There may be a maximum 32 controllers
already on the network segment.
Check on the InTouch panel, P.C. or
Parameter DIN Range/Units Default
HT(LT)
Dsgn Act.
Cut in Temperature 0 -49 to 30 / °C 0 (-20)
Differential Below 1 0 to 30 / °C 1.5 (2)
Air On / Off Weight 2 0 to 100 / % 50
OT Alarm 4 -49 to 60 / °C 5 (-16)
UT Alarm 3 -49 to 60 / °C -2 (-25)
Alarm Delay 5 00:00 to 99:00/Min:Sec 20:00
Log OT Alarm 8 -49 to 60 / °C 5 (-15)
Log UT Alarm 7 -49 to 60 / °C 0 (-25)
Log Probe Type: 0=Off ;
1=Product ; 2=Alarm ;
3=Prod/Alarm
6 0 to 3 0
Defrost Start 9 00:00 to 23:59/Hrs:Mins 01:00
Number of Defrosts per Day 10 0 to 8 6
No Defrost Time 11 0 to 25 / Hrs. 7
Gas Defrost Detect 12 0 to 30 / °C 18
Defrost Terminate Temperature 13 -49 to 30 / °C 10 (14)
Defrost Minimum Time 14 00:00 to 99:00/Min:Sec 05:00
Defrost Maximum Time 15 00:00 to 99:00/Min:Sec 24:00
(25:00)
Drain Down Time 16 00:00 to 20:00/Min:Sec 01:30
Defrost Recovery Time 17 00:00 to 99:00/Min:Sec 30:00
Defrost Type: 0=Elect.; 1= 2Gas
; 2= 3Gas
18 0 to 2 0
Defrost Mode: 0=Local ;
1=Remote
19 0 to 1 0
Defrost Hold: 0=Off ; 1=On 20 0 to 1 0
Hour 21 0 to 23
Minute 22 0 to 59
Day 23 0 to 31
Month 24 0 to 12
Year 25 0 to 99
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On
26 0 to 2 0
Door Alarm Delay 27 00:00 to 99:00/Min:Sec 20:00
Drip Pan Heater: 0=Off ; 1=On 28 0 to 1 0
Fans Off when Door is Open:
0=Off ; 1=On
29 0 to 1 0
Liquid Line Closed when Door is
Open: 0=Off ; 1=On
30 0 to1 0
Superheat reference 31 8.0 (6.0)
Proportional Gain 32 2.00
Integral Gain 33 Do not change the 2.00
Integral Time 34 value of these 03:00
EEV Size 35 parameters 1.0
Temp. Proportional Gain 36 1.5
Temp. Integral Gain 37 0.7
Temp. Integral Time 38 10:00
Manual Defrost: 0=Off ; 1=On 99 0 to 1 0
EET004c 7B30FE
Display Alarm Messages:
AL Temperature alarm
Ft Probes 1 and 2 are faulty
Pn probe ‘n’ faulty or not connected
(Where ‘n’ = probe number)
EE EEPROM fault
rr Internal program fault
En Plant fault (‘n’ = number)
Store:.............................................
Controller
Name:
Designer:........................................
Date:..............................................
Engineer:........................................
Date:..............................................
Comments:
Universal Controller-
Coldroom
ZA-10064-EET