EasyManuals Logo
Home>Honeywell>Control Unit>D06F

Honeywell D06F User Manual

Honeywell D06F
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
MU1H-1002GE23 R0315 12 Honeywell GmbH
GB
7. Assembly
7.1. Installation guidelines
Horizontal and vertical installation possible
Provide shut-off valve
If there are system parts on the outlet side which could
become overloaded with impermissibly high pressure in
the event of incomplete closure of the pressure reducing
valve, a safety valve must be fitted in accordance with
DIN EN 806-2 in conjunction with DIN 1988-200. The
outlet pressure of the pressure reducing valve in these
cases must be set at least 20% below the set pressure of
the safety valve.
The installation location be be frost-proof and easily
accessible
- Pressure gauge must be easily visible
- The degree of soiling on the transparent filter bowl must
be easily visible
- Easy to maintain and clean
For domestic water installations in which a high level of
protection from soiling is required, a fine filter should be
installed upstream of the pressure reducing valve
Calm-down distance of 5xDN before the pressure
reducing valve (in accordance with EN 806-2)
7.2. Assembly instructions
1. Rinse pipeline well
2. Plug in venturi nozzle (only 1
1
/
4
" / 2")
3. Install pressure reducing valve
Observe flow direction
Install free of tension and bending stresses
4. Screw in the sealing plugs manually
8. Start-up
8.1. Set the outlet pressure
8.1.1. D06F/D06F-LF, D06FN, D06FI
1. Close the shut-off valve on the input side
2. Reduce the pressure on the output side (e.g. by draining
water)
3. Close the shut-off valve on the output side
4. Loosen slotted screw
Do not unscrew the slotted screw
5. Slacken the pressure spring
Turn the adjuster knob (grey) anti-clockwise (-) as far as
it will go
6. Slowly open the shut-off valve on the input side
7. Turn the adjuster knob until the setting scale displays the
desired value
8. Re-tighten the slotted screw
9. Slowly open the shut-off valve on the output side
8.1.2. D06FH
1. Close the shut-off valve on the input side
2. Reduce the pressure on the output side (e.g. by draining
water)
3. Close the shut-off valve on the output side
4. Loosen the slotted screw and unscrew completely
5. Remove the red handle
6. Slacken the pressure spring
Turn the adjuster knob (grey) anti-clockwise (-) as far as
it will go
7. Slowly open the shut-off valve on the input side
8. Turn the adjuster knob until the setting scale displays the
desired value
9. Replace the red handle
10. Re-tighten the slotted screw
11. Slowly open the shut-off valve on the output side
9. Maintenance
According to DIN EN 806-5, the following works must be
performed:
9.1. Inspection
9.1.1. Pressure reducing valve
1. Close the shut-off valve on the output side
2. Check the outlet pressure with zero flow using a pressure
gauge
If the pressure increases gradually, then the tap is
either soiled or defective. In this case, carry out
maintenance and cleaning
3. Slowly open the shut-off valve on the output side
9.2. Maintenance
9.2.1. Pressure reducing valve
9.2.1.1. D06F, D06F-LF, D06FN, D06FI
1. Close the shut-off valve on the input side
2. Reduce the pressure on the output side (e.g. by draining
water)
3. Close the shut-off valve on the output side
4. Loosen slotted screw
Do not unscrew the slotted screw
5. Slacken the pressure spring
Turn the adjuster knob (grey) anti-clockwise (-) as far as
it will go
6. Unscrew the spring bonnet
Use double ring wrench ZR06K
Set the outlet pressure at least 1 bar below the inlet
pressure.
We recommend entering into a maintenance contract
with an installation company
Interval: 1 x yearly
In accordance with DIN EN806-5 and VDI 3810-2,
Pressure reducing valves must be inspected and
serviced annually.
Filter inserts must be replaced at six-monthly intervals.
Maintenance works must be carried out by an
installation company.
Caution!
There is a pressure spring in the spring bonnet. If the
pressure spring is projected, it can cause injuries.
Ensure that the pressure spring is not tensioned!

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell D06F and is the answer not in the manual?

Honeywell D06F Specifications

General IconGeneral
BrandHoneywell
ModelD06F
CategoryControl Unit
LanguageEnglish

Related product manuals