Excel 800 LION
13 EN1B-0375GE51 R0308
XW885 Cable Details
12
3678
4
5
RJ45 plug with clip at front
RS232 plug
sub-D male of laptop
SHIELD
+5V
Fig. 7 CLLIONLC01/laptop cable details
XW582 Cable Details
to XC5010C XI582
1
5
4
3
2
9
8
7
6
Fig. 8 XW582 cable details
XW585 Cable Details
to XC5010C
1
5
4
3
2
9
8
7
6
+5V
Fig. 9 XW585 cable details
XW586 Cable Details
123678 4
5
SHIELD
RJ45 plug with clip at front
+5V
Fig. 10 XW586 cable details
L
ON
W
ORKS
Bus Termination Modules
Type Description
209541 L
ON
W
ORKS
Bus termination module
XAL-Term L
ON
W
ORKS
connection and
termination module, which can be
mounted on DIN rails and in fuse
boxes
Table 15 L
ON
W
ORKS
Bus termination modules
Cable Specifications
Power Supply Cables
When checking the length of the power supply cable, the
connection cables to all I/O modules must be taken into
account.
Max. length
3 m (per side of the controller),
see Fig. 32 on page 25
Cross section
min. 0.75 mm
2
(AWG 18)
Table 16 Power supply cables specification
Panel Bus Cables
Max. length
40 m
Cable type
twisted pair, e.g., J-Y-Y 2 x 2 x 0.8
Table 17 Panel Bus cables specification