I/O Bus Switch S2
The CLLIONLC01
Controller Module features a 2-position
I/O Bus switch S2.
I/O Bus switch S2 must be set in accordance with the kind
of I/O modules connected to communication terminals
71, 72 and 75, 76 of the controller module.
Terminals 71, 72 and 75, 76 must be all connected either to
Panel Bus I/O modules or to L
ON
W
ORKS
Bus I/O modules.
The default setting is Panel.
Fig. 55 I/O Bus switch S2
Communication S2 setting
L
ON
W
ORKS
Bus only LON
Panel Bus and L
ON
W
ORKS
Bus
L
ON
W
ORKS
B
US
modules connected to
terminals 11 …. 14 of the controller
Panel
Panel Bus connected to terminals 71, 72
or 75, 76 of the controller
Panel
Table 38 I/O Bus switch settings
C-Bus Termination Switch S1
The CLLIONLC01
Controller Module features a 3-position
C-Bus termination switch S1.
This switch must be set in accordance with the given C-Bus
configuration.
Fig. 56 C-Bus termination switch
Switch
setting S1
Baud rate
9.6k all
Up to 9600 baud (default setting)
76k mid Up to 76800 baud without bus termination
76k end
Up to 76800 baud with bus termination
controller at the end of the C-Bus
Table 39 CLLIONLC01
C-Bus termination switch S1
settings
Memory
Memory Size Usage
SRAM 512 KB For controller application,
modem trend and firmware
RACL application: 128 KB
Total application: 192 KB
Flash 2 MB Firmware (1 MB) and
application (1 MB) storage
EPROM 128 KB For bootstrap loader
Table 40 CLLIONLC01 memory
Note
The CLLIONLC01
Controller Module does not contain a
battery. RAM (data and realtime clocktime) is buffered for
3 days by a super capacitor.