5. Cables
5.3. Antenna Lightning Arrestors
12 SmartLine Wireless Transmitter Professional Installation Guide Revision 1
5.3 Antenna Lightning Arrestors
Table 5-4 Lightning Arrestor Specifications for Remote Antenna(s)
Honeywell
Part
Number
Manufacturer
Manufacturer
Part Number
Specification
Connector
Type
Frequency
(GHz)
Attenuation
(dB)
50018279-
090
ALTELECON
AL-NFNFB-9
50 ohm
N Female
to N
Female
0 – 3
0.4 (max)
The lightning surge arrestor must be properly grounded in order to perform per specification.
Connecting to local ground using a No. 12 (4 mm
2
) copper conductor is recommended. See the
installation manual for other details.
Figure 5-1 Lightening Surge Arrestor (Altelecon AL-NFNFB-9) 50018279-090