Installation Instruction VARIODYN
®
D1 System
FB 798663.GB0 / 05.19 23
Features
Approved in accordance with EN 54-17 (included in the EN 54-16 approval of the VARIODYN
®
D1 System)
Up to 4 rings per DOM4-8 or DOM4-24
Up to 500 W power per loop
Up to 5 spurs with more than one loudspeaker per loop (including EOL)
Easy migration of existing spurs into the loop
Fully fail-safe if each loudspeaker is fitted with an LIM
Replaces A/B cabling
Partially eliminates the need for E 30 cabling (DIN VDE 0833-4, chapter 7.10)
Various standard cable types can be used for loudspeakers
Cable leads can be wired in parallel to increase the cable cross-section - Do not route outbound and inbound
loop conductors in the same cable or the same conduit
Amplifier Maximum number of LIMs Max loop length including spur lines
2XD250 40 1000
2XD400 64 1000
4XD250B 25 500
4XD300 40 1000
4XD500 50 1000
No other amplifiers are approved for combination with LIMs
Observe the maximum number of LIMs and the loop length for the amplifier used
20 % power reserve per amplifier should be planned in
The maximum load is different for each amplifier and should be determined in consultation with
the Technical Support.
Three operating modes can be implemented with a DOM4-8 or DOM4-24:
Fig. 14: Operation with
up to 4 loop
Fig. 15: Operation with
up to 8 spurs
Fig. 16: Mixed operation, e.g. with 2 loops
and 4 spurs (example)