WEB/CP-202-XPR AND WEB/CP-602-XPR CONTROLLERS
95-7775—01 4
Power Input
Integrated power supply for 24 V input, using either a dedicated, external, Class-2, 24 Vac transformer or a 24 Vdc power
supply, 40 W maximum.
Includes integral rechargeable NiMH backup battery pack, for short duration AC power fail operation.
Connection for external, rechargeable, 12V sealed lead-acid battery, for continuous system operation over longer power
outages. Provides trickle charge and monitoring support to customer-supplied battery.
GPRS Modem (WEB/CP-202-XPR-GW and WEB/CP-602-XPR-GW only)
Factory-installed GSM cellular modem using GPRS (General Packet Radio Service) data technology.
An LED on the front left cover indicates modem status.
Uses GSM/GPRS quad-band SMA coax-mounted stub antenna, mounted on left side of unit. If needed, an extension SMA
coax cable can be used to the antenna, or another external antenna used instead.
Operating System
QNX RTOS, IBM J9 Java
®
Virtual Machine.
•JACE
®
(Java Application Control Engine) Niagara
AX
software (AX-3.4.51 or later required).
Chassis and Enclosure
Plastic wall mount chassis, with two removable front covers secured by screws.
Cooling by internal air convection.
Dimensions: 12.625 in. (320.7mm) tall
x 7.5 in. (190.5mm) wide x 2.25 in. (57.2mm) deep.
Weight: Net 2.1 lbs. (0.95 kg), Gross 3 lbs. (1.36 kg)
Environment
Operating temperature range: 0 to 50°C (32 to 122°F).
Storage temperature range: 0 to 70°C (32 to 158°F).
Relative humidity range: 5% to 95% at 25°C (77°F), non-condensing.
Agency Listings
UL 916
C-UL listed to Canadian Standards Association (CSA) C22.2 No. 205-M1983 “Signal Equipment”
CE, FCC part 15 Class A
BTL B-BC BACnet Building Controller listed when the BACnet driver is installed and configured
PREPARATION
Unpack the controller and inspect the package contents for damaged or missing components. If damaged, notify the appropriate
carrier at once and return any damaged components for immediate repair or replacement. See “Returning a Defective Unit” on
page 31.
Additional information applies, as follows:
Included in this Package
Material and Tools Required
Included in this Package
Included in this package you should find the following items:
The controller, with both cover halves fastened.
These WEB/CP-202-XPR and WEB/CP-602-XPR Installation Instructions, form 95-7775.
A hardware bag containing the following items:
Two (2) 7-position screw terminal blocks, for UIs (universal inputs).
Three (3) 6-position screw terminal blocks, one for AOs (analog outputs), one for DOs (digital outputs),
one for RS-485/15V power to optional remote modules (3 terminals RS-485, 3 for power).
One (1) 2-position screw terminal block for external 12V sealed lead-acid battery (not provided).
A GSM/GPRS coax-mounted stub antenna (for units ordered with integral GPRS modem).
If a WEB/CP-202-XPR-GW or WEB/CP-602-XPR-GW model controller, a SIM card provisioned by the Wyless Group.