XNX Universal Transmitter Quick Start Guide
31
Searchline Excel and Searchpoint Optima Plus Remote Installation
Junction Boxes are available for the Searchline Excel and Searchpoint Optima
Plus to facilitate remote mounting from the XNX Universal Transmitter. Junction
boxes are available for installations requiring UL/CSA or ATEX approvals. Consult
the Searchline Excel Technical Handbook (2104M0506) or Searchpoint Optima
Plus Operating Instructions (2104M0508) for specifics on remote installations or
contact your Honeywell Analytics representative for more information.
For remote mount installations, the maximum distance between the XNX
Universal Transmitter and the Searchpoint Optima Plus unit is 33m (100 ft.),
using 18 gauge wire.
Searchpoint Optima Plus or Searchline Excel Wiring Recommendations
When wiring the XNX and the Searchpoint Optima Plus or Searchline Excel for
remote applications, the General Recommendations of the ANSI/TIA/EIA-485-A
standard must be adhered to with the following additions:
1. WhenmountingtheSearchlineExcelorSearchpointOptimaPlus,
runwiringconnectionsbetweeneachExcelorOptimaandtheXNX
inadedicatedseparateconduit.
2. Use18AWGtwistedshieldedcablefortheRS485connection
betweenExcelorOptimaandtheXNX.Makesurethattheshieldof
thecableisgroundedtoearthandXNXgroundononeendONLY.
3. Avoidrunningwiringnearmaincablesorotherhighvoltage
equipment.
4. DONOTAPPLY120Ohmterminatingresistors.Theseresistorsare
notrequiredduetolowdatarates.
5. HArecommendsthatExcelorOptimaandtheXNXbewiredto
buildingground.Thesystemshouldbegroundedatonepointonly.
INSTALLATION TIP:
Always issue a soft reset after connecting the Optima and XNX for the rst time. The
soft reset is performed by accessing the XNX calibration menu.
NOTE:
When the soft reset is initiated for the Optima IR Sensor, the RS-485
communication will be interrupted temporarily and faults F120 and/or
F161 may be observed. RS-485 communication will be re-established
in a few minutes and the faults will be reset automatically in the Non-
Latching Mode. The faults must be reset manually in the Latching Mode.

Table of Contents

Other manuals for Honeywell XNX-UT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XNX-UT Series and is the answer not in the manual?

Honeywell XNX-UT Series Specifications

General IconGeneral
BrandHoneywell
ModelXNX-UT Series
CategoryTransmitter
LanguageEnglish

Related product manuals