XNX Universal Transmitter Quick Start Guide
42
6.3 Configuring the XNX Universal Transmitter
The XNX Universal Transmitter can be configured via the front panel by using
the menus available in the Configure Menu. For information on accessing and
navigating the menus, see Section 7.1 - Controls and Navigation.
TheXNXisshippedwiththefollowingsettings:
Display Language
English
Date Format
mm/dd/yy
Time Format
HH:MM
mV Sensor Type (w/mV
personality)
MPD-IC1 (%Vol)
Alarm Levels
Sensor Cartridge Dependent
Latching/Non-Latching Alarms
Alarm: Latching
Fault: Non-Latching
Display Units
PPM, %VOL or %LEL
(dependent on personality and sensor choice)
4-20 mA Levels
1
Inhibit: 2.0 mA
Warning: 3.0 mA
Overrange: 21.0 mA
Calibration Interval
180 Days (HA recommends 30 day interval)
Unit ID
XNX #nnnnnnnn
Relay Settings
Alarm Normally De-Energized
Fieldbus
Settings
HART
®
Address: 0
Mode: Point-To-Point
Modbus
®
(if installed)
Address: 5
Baud Rate: 19200
Level 1 Password Access
0000
Level 2 Password Access
0000
Easy Reset Enabled
Yes