lp-505 Rev. 000 Rel. 015 Date 1.7.20
57
3. Inlet / DHW / Operating Temperature / Exhaust Sensors
Figure 55 - Inlet / DHW / Operating Temperature Sensors Error Analysis Tree
C. Suggested Corrective Actions
Problem Possible Causes Possible Remedies
No electrical power to the water
heater
1. Is the plug on the power supply cord unplugged
from the electrical outlet?
2. Is electrical panel’s 10 Amp circuit breaker
tripped?
3. Is the fuse on the circuit board good?
4. Is there a power outage to the home?
1. Reset the plug.
2. Reset the circuit breaker.
3. If the display panel is blank, unplug the unit or
contact a qualied installer / service technician.
4. Contact the power company.
No water available when faucet is
opened
1. Is the water supply valve shut o at the meter (do
cold water faucets work)?
2. Is the water supply valve near the unit open?
3. Is the water pipe frozen?
4. Is an error code ashing on the display panel
(leak detected)?
1. Open the closed supply valve.
2. Open the water supply valve.
3. Turn OFF the unit, close all water valves and
the gas valve. Contact a qualied installer /
service technician.
4. Refer to error code information and contact a
qualied installer / service technician.
Hot water is not available when a
faucet is opened
1. Does the water heater have power (plugged in)?
2. Is the water heater turned ON?
3. Is an error code ashing on the display panel?
4. Is the gas supply valve open or shut o at the
meter (do other gas devices work)?
1. Restore electrical power to the unit.
2. Press and hold the Power button to turn the
unit ON.
3. Refer to the Diagnostic and Error Codes
section in this manual.
4. Open the gas supply valve.
The water temperature is not hot
enough or turns cold during use
1. Is the faucet open enough to draw at least 0.5
gallons (2.2L) per minute through the water heater?
2. Is an error code ashing on the display panel?
3. Is the outlet water temperature set too low?
1. Open the faucet to allow more water ow.
2. Refer to the Diagnostic and Error Codes
section in this manual.
3. Adjust the outlet water temperature (refer to
the procedure in this manual).
It takes a long time before hot
water ows from the faucet
Is the faucet some distance from the water heater?
1. Have recirculation valves and/or plumbing
return line(s) installed and program the unit for
external recirculation mode.
2. Allow time for the cold water already in the
pipes to ow from the faucet.
The water is not hot enough Is the water temperature set too low? Adjust the temperature setting.
The water at the faucet is too hot Is the water temperature set too high? Adjust the temperature setting.
A fan can be heard even when the
unit is not operating
1. The fan continues to operate after the burner
shuts o to clear the exhaust vent of combustion
gases.
2. The fan may run to help prevent freezing.
1. This is normal operation – no action is
required.
2. Protect the water heater from freezing
temperatures or shut o and drain the unit.
White “smoke” can be seen coming
out of the exterior exhaust gas
vent
Depending on the outside temperature, water
vapor can be produced as the exhaust is vented.
This is normal operation – no action is required.
Table 35 - Troubleshooting Chart