UPS2000-G-(1 kVA-3 kVA)
User Manual
4 Setting Control Panel
Copyright © Huawei Technologies Co., Ltd.
56
Alar
m ID
Alarm
Cause
ID
Alarm
Name
Alarm
Severity
Alarm Clear
Mode
Trigger
Condition
Impact on
the
System
Repair Proposal
progress.
9E
1
On
bypass
Minor
This alarm is
automatically
cleared.
The
inverter
is not
started.
The load
power
exceeds
the rated
inverter
loading
capability
.
The
temperatu
re
exceeds
the rated
temperatu
re.
If the
bypass is
abnormal,
the UPS
may power
off.
Check whether
other alarms
are generated.
If other alarms
are generated,
clear them.
If there are no
other alarms,
start the
inverter
manually.
9F
1
On
battery
Minor
This alarm is
automatically
cleared.
The mains
input is
abnormal.
When the
UPS works
in battery
mode, the
UPS may
power off if
the batteries
are
abnormal.
Check the mains
input. If the mains
input is abnormal,
wait until the
mains input
recovers.
4.8 Alarm Indication
Table 4-7 Alarm indication
Alarm
Display (Blinking)
Buzzer
Insufficient battery capacity
Beeps once every second.
Overload
Beeps twice every second.
Battery disconnection
Beeps once every second.

Other manuals for Huawei UPS2000-G-2KRTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G-2KRTL and is the answer not in the manual?

Huawei UPS2000-G-2KRTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-G-2KRTL
CategoryUPS
LanguageEnglish

Related product manuals