UPS2000-G-(1 kVA-3 kVA)
User Manual
9 Specifications
Copyright © Huawei Technologies Co., Ltd.
74
9.4 Bypass Input Electrical Specifications
Table 9-4 Bypass Input Electrical Specifications
Item
1 kVA
2 kVA
3 kVA
Bypass voltage
tolerance
170 V 264 V AC
Bypass frequency
tolerance
4753 Hz or 5763 Hz
Bypass overload
capability
110%120%, 30 minutes
120%130%, 10 minutes
130%150%, 1 minute
Input mode
One mains input
The upper and lower thresholds of bypass voltage tolerance are configurable on the LCD.
9.5 Output Electrical Specifications
Table 9-5 Output electrical specifications
Item
1 kVA
2 kVA
3 kVA
Rated capacity
1000 VA/800
W
2000 VA/1600
W
3000 VA/2400
W
Output power factor (PF)
0.8
Rated output voltage
200 V AC/208 V AC/220 V AC/230 V AC/240 V
AC
Output voltage tolerance
±1%
Output frequency range
In normal mode, the UPS output frequency is
consistent with the input frequency, which is 50
Hz or 60 Hz with the tolerance of ±3 Hz.
In battery mode, the frequency is 50 Hz or 60 Hz
(tolerance ±0.05%).
Total distortion of output voltage
waveform (THDv)
< 6% (non-resistive load)
< 3% (resistive load)
Crest factor
A maximum of 3:1
Inverter overload capability
When the ambient temperature is 035°C:
105%110%: The UPS automatically shuts
down (in battery mode) or transfers to bypass

Other manuals for Huawei UPS2000-G-2KRTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G-2KRTL and is the answer not in the manual?

Huawei UPS2000-G-2KRTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-G-2KRTL
CategoryUPS
LanguageEnglish

Related product manuals