Output(AC)
Rated Power(W) 3680 4000 5000 6000 6500
Max. apparent AC
power(VA)
3680 4400 5000 6000 6600
Rated grid
voltage(Vac)
220/230/240 220/230/240
Rated power
frequency(HZ)
50/60 50/60
Max. output
current(A)
16 20 23 27.3 29.6
Adjustable
displacement power
factor
0.8ind to 0.8cap 0.8ind to 0.8cap
THDi at rated power <3% <3%
Efficiency
Max. Efficiency 97.90% 97.90% 97.90% 98.00% 98.00%
Euro Efficiency 97.40% 97.40% 97.40% 97.50% 97.50%
Protection
Anti-islanding
Protection
Intergrated Intergrated
Input Reverse Polarity
Protection
Intergrated Intergrated
Insulation Resistor
Detection
Intergrated Intergrated
Residual Current
Monitoring Unit
Intergrated Intergrated
Output Over Current
Protection
Intergrated Intergrated
Output Short
Protection
Intergrated Intergrated
Output Over Voltage Intergrated Intergrated