1-13
BOILER SYSTEMS AND OPERATION
CONTROLLER MANUAL – SFC/SFB SERIES BOILERS
TABLE OF PARAMETERS
PARAMETER DESCRIPTION DEFAULT RANGE / OPTIONS
P001 System Type SFC = 0
SFT = 2
SFB = 3
0 = CH + DHW
direct
1 = CH + External
indirectly heated
tank
2 = DHW direct only
3 = CH only
4 = Combi +
External indirectly
heated tank. Tank
differential 9°F /
5°C.
5 = Combi +
External directly
heated tank Tank
differential 9°F / 5°C
P003 Units 1 0 = Metric (°C, L/S,
Bar)
1 = Imperial (°F,
gpm, PSI)
P010 Maximum Space
Heating Output
SFC 125 = 75
All other models
= 100
25-100
P013 Maximum %
indirect tank
output
80%
P030 Space Heating
Pump Setting
0 0 = Post-purge time
active
1 = continuous
(DHW comfort
function off)
P031 Space Heating
Pump Maximum
Capacity
65 15%-100% (but
cannot be below
setting P032)
P032 Space Heating
Pump Minimum
Capacity
35 15%-100%