SERVICING
Independent - Installation and Servicing
46
FLAME DETECTION ELECTRODE REPLACEMENT
47
SPARK GENERATOR REPLACEMENT
1. Refer to Frame 40.
2. Disconnect the leads from the spark
generator.
3. Remove the M5 screws securing the
spark generator to the boiler chassis.
4. Fit the new spark generator and re-
assemble in reverse order ensuring
the two earth leads are correctly
replaced.
5. Check operation of the boiler. Refer
to Frames 29 & 30.
Flame Detection Electrode
Spark Generator
12.5mm
Straight edge
1. Refer to Frame 40.
2. Remove the burner. Refer to Frame 43.
3. Unplug the ame detection lead from the
electrode.
4. Remove the 2 screws retaining the detection
electrode.
5. Remove the electrode.
6. Fit the new ame detection electrode, using the
new gasket supplied.
7. Reassemble in reverse order.
8. Check the operation of the boiler. Refer to
Frames 29 & 30.