Goodrive100-PV Series Solar Pumping VFD Safety precautions
2
1.3 Safety guidelines
Only qualified electricians are allowed to operate on the VFD.
Do not carry out any wiring and inspection or changing components when
the power supply is applied. Ensure all input power supply is disconnected
before wiring and checking and always wait for at least the time designated
on the VFD or until the DC bus voltage is less than 36V. Below is the table
of the waiting time:
Do not refit the VFD unauthorized; otherwise fire, electric shock or other
injury may occur.
The base of the radiator may become hot during running. Do not touch to
avoid hurt.
The electrical parts and components inside the VFD are electrostatic. Take
measurements to avoid electrostatic discharge during relevant operation.
1.3.1 Delivery and installation
Please install the VFD on fire-retardant material and keep the VFD away
from combustible materials.
Do not operate on the VFD if there is any damage or components loss to
the VFD.
Do not touch the VFD with wet items or body, otherwise electric shock may
occur.
Note:
Select appropriate moving and installing tools to ensure a safe and normal running of the
VFD and avoid physical injury or death. For physical safety, the erector should take some
mechanical protective measurements, such as wearing safety shoes and working uniforms.
Do not carry the VFD by its cover. The cover may fall off.
Ensure to avoid physical shock or vibration during delivery and installation.
Install away from children and other public places.
The VFD cannot meet the requirements of low voltage protection in IEC61800-5-1 if the
altitude of installation site is above 2000m.
The leakage current of the VFD may be above 3.5mA during operation. Ground with proper
techniques and ensure the grounding resistor is less than 10Ω. The conductivity of PE
grounding conductor is the same as that of the phase conductor (with the same cross
sectional area).