Goodrive100-PV Series Solar Pumping VFD Options and use
67
A.3 Cables
A.3.1 Power cables
Dimension the input power and motor cables according to local regulations.
Note: A separate PE conductor is required if the conductivity of the cable shield is not
sufficient for the purpose.
A.3.2 Control cables
The relay cable needs the cable type with braided metallic screen.
Keypads need to be connected with network cables. The network cables must be shielded in
complicated electromagnetic environments.
Communication cables must be shielded twisted pairs.
Note:
Run analog and digital signals in separate cables.
Check the insulation of the input power cable according to local regulations before
connecting to the drive.
Recommended power cables for standard VFD models
Model
Recommended cable size
(mm
2
)
Terminal
screw
Tightening
torque
(Nm)
(+)/(-), R/S/T, U/V/W
PE
GD100-0R4G-S2-PV
1.5
1.5
M4
0.8
GD100-0R7G-S2-PV
1.5
1.5
M4
0.8
GD100-0R4G-SS2-PV
1.5
1.5
M4
0.8
GD100-0R7G-4-PV
1.5
1.5
M4
0.8
GD100-1R5G-4-PV
1.5
1.5
M4
0.8
GD100-2R2G-4-PV
1.5
1.5
M4
0.8
GD100-1R5G-S2-PV
2.5
2.5
M4
0.8
GD100-2R2G-S2-PV
2.5
2.5
M4
0.8
GD100-0R7G-SS2-PV
2.5
2.5
M4
0.8
GD100-1R5G-SS2-PV
2.5
2.5
M4
0.8
GD100-2R2G-SS2-PV
2.5
2.5
M4
0.8
GD100-004G-4-PV
2.5
2.5
M4
1.21.5
GD100-5R5G-4-PV
2.5
2.5
M4
1.21.5
GD100-1R5G-2-PV
2.5
2.5
M4
1.21.5