Goodrive100-PV Series Solar Pumping VFD Function parameters
55
Detailed illustration of parameters
factory delivery) as model -2, P15.39
must be set to 2.
0: -SS2 220V; single-phase input;
single-phase output
1: -S2 220V; single-phase input;
three-phase output
2: -2 220V; three-phase input;
three-phase output
3: -4 380V; three-phase input;
three-phase output
Setting range: 0–3
Current of the
main winding
It is the current of the main winding
when applying capacitance-removing to
control the single phase motor.
0.00–100.00A
Current of the
secondary winding
It is the current of the secondary
winding when applying
capacitance-removing to control the
single phase motor.
0.00–100.00A
P18 Group State viewing special for solar inverters
MPPT is implemented at the inverter
side. This value is determined at the
inverter side.
It is transferred from the boost module
or equal to the bus voltage.
The value displays the minimum voltage