Start up
6 720 643 409 (2010/03)
47
12 Start up
The first time the heat pump is started, a number of
settings are displayed automatically so as to facilitate
putting it in operation.
Before this stage, the heat pump should be installed in
accordance with the previous sections (Æ Chapter 9,
Æ Chapter 10). Collector circuits, heating circuits and
hot water circuits should be filled and aired.
The settings are also available under ordinary installer
menus.
Language and Operating mode
B Select language for the menus of the control unit
(Æ Chapter 15.10).
B Select operating mode (L/W + electric additional
heat)
(Æ Chapter 4.4, Æ Chapter 15.7).
Start-up
Review and adjust, as required, the functions below. See
the references for description of the functions.
B Set the following for each heat pump (compressor):
Acknowledge phase guard (Æ Chapter 15.9).
Hot water production (Æ Chapter 15.2).
B Set the heat pump output for each heat pump in Heat
pump x capacity (Æ Chapter 15.7). See the type
plate.
B Set Minimum outdoor temperature (Æ Chapter
15.1).
B State if Groundwateris used.
B Set Circuit 1 Heating\ Type of heating system (Æ
Chapter 15.1).
B Set Circuit 1 Cooling (if Cooling has been installed,
optional), see the documentation of options.
B Set Circuit 2, 3...(Æ Chapter 15.1) (option).
Mixing valve mode
Type of heating system
Mixing valve running time
B Select option in Protective anode installed (Æ
Chapter 15.2).
B
Set values for Pool (if pool has been installed), see
the documentation for options.
B Set Date (Æ Chapter 15.10).
B Set Time (Æ Chapter 15.10).
B Start-up completed, Yes/No.
The start-up menus will be available until Yes is
entered.
After the start-up menus, the Initial menu is shown in the
display. All customer functions are accessible from this
menu, whereas the installer menus are accessible only
after change of access level.
Fig. 50 Initial menu
Only functions which are identified by the
control unit are displayed in the initial
menu.
The start-up menus are available until Yes is
entered in Start-up completed.
B Read the complete menus before start-
up.
B A selection must be made in Heat pump x
capacity and Protective anode installed.
The selected system solution would
normally require a review of more settings
than the ones in the start-up.
6 720 614 789-01.1I