Settings
6 720 645 172 (2010/07) en
11
4.2 Settings\Addressing
4.3 Settings\Room temperature
Setting Factory Range HP
Addressing
Heat pumps
Number:
This HP:
1
E21
1- 9
E21- E29
E21
E2x
B Set the number of heat pumps in E21.
B State the valid designation of the heat pump in each heat pump in accordance with the system drawing.
By setting Number and This HP all cooperation, addressing and port setting is arranged automatically.
Tab. 31 Addressing
Setting Factory Range HP
Room temperature
Summer/winter
op.
Summer operation
Start:
T2 >
in
17 °C
180 min
E21
Winter operation
T2 <
in
15 °C
300 min
E21
Winter operation
Direct start:
T2 < 7 °C
E21
B Set the outdoor temperature that is required for changeover to summer operation, and the delay
that applies.
B Set the outdoor temperature that is required for changeover to winter operation, and the delay
that applies.
B Set the outdoor temperature at which winter operation shall start directly, without a delay.
Delays prevent repeated stops and starts of the heating system circulation pump when the outdoor
temperature fluctuates above and below the limit.
Basic setting Basic setting
DOT
Min
Max
-35 °C
20 °C
60 °C
E21
The factory settings refer to radiator systems. For underfloor heating systems only, 35 °C is
recommended as the highest flow set point. Other applications may require other values.
B Set the minimum outdoor temperature for the heat curve (DOT), and the lowest and highest flow
temperature set points.
Heat curve E21
The flow temperature set points at different outdoor temperatures are automatically calculated using
the values in Basic setting, Æ Chapter 4.3.1 for example on heat curve for radiator systems and
underfloor systems. Values can be changed individually, for example adjusting the heat curve at 0 °C.
Parallel offset
Parallel offset 0 K E21
B Enter by how many degrees the flow temperature at the curve's outdoor temperatures shall be
adjusted down or up.
Tab. 32 Room temperature