EasyManuals Logo
Home>IVT>Thermostat>Rego 5101

IVT Rego 5101 User Manual

IVT Rego 5101
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
Settings
6 720 645 172 (2010/07) en
22
In Own heat
curve
Own heat curve
Actual v.:
Set point:
Settings> Own heat curve
P:
I:
Deviation:
Pump:
Display
C
0
0
0 K
Off Winter, Summer, Off, On
E21
B Set the heat curve that shall apply for the unit in Set point curve.
B Set appropriate values for P and I.
B Set the temperature deviation that shall cause an alarm Accessory x temp. deviation
(Æ Chapter 5.6.51, page 36).
B Enter pump function. Winter means that the accessory circulation pump is in operation during winter
operation.
The unit uses an externally connected sensor to control a 0-10V connected mixing valve to maintain
the set point value according to settings in Set point curve.
In E11 heat
curve
E11 heat curve
Actual v.:
Offset:
Settings> E11 heat curve
P:
I:
Deviation:
Pump:
Display
0 K
0
0
0 K
Off Winter, Summer, Off, On
E21
B Set appropriate values for P and I.
B Set the temperature deviation that shall cause an alarm Accessory x temp. deviation
(Æ Chapter 5.6.51, page 36).
B Enter pump function. Winter means that the accessory circulation pump is in operation during winter
operation.
The unit uses an externally connected sensor to control a 0-10V connected mixing valve to maintain
the set point value according to the heat curve for E11.T1.
In Fixed sp
cooling
Fixed sp cooling
Actual v.:
Set point:
Settings> Fixed sp cooling
P:
I:
Deviation:
Pump:
Display
C
0
0
0 K
Off Winter, Summer, Off, On
E21
B Set the fixed set point value that must apply.
B Set appropriate values for P and I.
B Set the temperature deviation that shall cause an alarm Accessory x temp. deviation
(Æ Chapter 5.6.51, page 36).
B Enter pump function. Summer means that the accessory circulation pump is in operation during
summer operation.
The unit uses an externally connected sensor to control a 0-10V connected mixing valve to maintain
the stated fixed set point value.
Setting Factory Range HP
Tab. 37 Accessory

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IVT Rego 5101 and is the answer not in the manual?

IVT Rego 5101 Specifications

General IconGeneral
BrandIVT
ModelRego 5101
CategoryThermostat
LanguageEnglish