Jetson
www.JetsonHVAC.com
71
new file and press OPEN. The file will be
uploaded to the controller. The controller will
reboot itself.
Routine software (HEX FILE) updates are NOT
necessary. However, if a software update is
necessary to resolve an operating issue, a hex file
in a zipped folder will be provided. Save the
zipped folder to the computer’s desktop. Right
click folder and select EXTRACT ALL. This will
create another folder by the same name on the
computer’s desktop. Inside this folder will be the
hex file. It should be about 2300 KB. In the MCS-
CONNECT software, select TRANSMIT SW.
Locate the extracted hex file and select Transmit.
Watch the chiller LCD screen. After the file is
uploaded, the FWCD unit controller will verify
that it’s a valid file and then erase the flash
memory. Next, it will write the new hex to
memory. When completed, the controller will
reboot itself. This process may take 15 or 20
minutes. After the reboot is completed, close and
restart the MCS-CONNECT software to
reestablish communication with the chiller.