Unit Start-Up Procedures
Start-up and commissioning must be performed by
a factory authorized Jetson service technician.
Pre-Start
Complete each step in the “Pre-Start Up
Procedures” included in the FWCD Individual
Chiller Start-up Check List and check off each step
as completed.
Hazardous Voltage!
Failure to disconnect power before servicing
could result in death or serious injury.
Disconnect all electric power, including
remote disconnects before servicing. Follow
proper lockout/tagout procedures to ensure
the power cannot be inadvertently
energized.
Equipment Damage!
• To prevent overheating at connections
and under- voltage conditions at the
compressor motor, check tightness of all
connections in the compressor power
circuit.
• To prevent compressor damage, do not
operate the unit with discharge or liquid
line service valves closed.
• The use of untreated or improperly
treated water in a Chiller may result in
scaling, erosion, corrosion, algae or
slime. It is recommended that the
services of a qualified water treatment
specialist be engaged to determine what
water treatment, if any, is required.
Jetson assumes no responsibility for
equipment failures which result from
untreated or improperly treated water, or
saline or brackish water.
• To prevent evaporator or condenser
damage, pipe strainers must be installed
in the water supplies to protect
components from water born debris.
Jetson is not responsible for equipment
damage caused by water born debris.