6. Press Confirm to save locally and on USB. The setting files are named based on the TEC3000
model name, date, and time stamp (for example, TEC3x1x-00_2018-07-01T1). The files are saved
locally and on the USB drive’s root directory. See Table 15 if the settings are not backed up
correctly.
7. After the settings are saved onto the USB drive, remove the USB drive from the TEC3000.
Restoring the settings
About this task:
If the TEC3000 is connected to a network (for example, MSTP or wireless), you must manually set or
verify the BACnet
®
Instance ID and BACnet Address, or both, in the Network Setup page after the
restore so they do not conflict with other devices on the same network.
1. Ensure that the TEC screen is on.
2. Insert the USB drive into the right side of the TEC. See Figure 1 for the USB port location.
3. Press the Menu icon.
4. Press Update.
5. Press Restore.
6. Select Local Storage or the correct configuration file created from a previous backup operation.
The setting files are named based on the TEC3000 model name, date, and time stamp (for
example, TEC3x1x-00_2018-07-01T1). The files are saved locally and on the USB drive’s root
directory.
7. Press Confirm if you have the correct file name. The settings are loaded from the USB drive.
8. After the settings are loaded from the USB drive, remove the USB drive from the TEC3000.
Choosing the Communication mode (TEC3612 and TEC3613 Models)
1. Ensure the TEC screen is on.
2. Press the Menu icon.
3. Press Setup.
4. Press Network Setup.
5. Press FC Comm Mode.
6. Select BACnet or N2 by pressing the up and down arrows.
7. Proceed to Step 8 to perform BACnet communication and Step 16 to perform N2
communication.
8. Press the back arrow to return to the previous screen.
9. Press BACnet Instance ID.
10. Enter the unique BACnet
®
instance ID using the keypad. This value should be different to the
other controllers on the site.
11. Press Save.
12. Press the back arrow to return to the previous screen.
13. Press BACnet Address.
14. Enter the BACnet MS/TP address through the keypad.
15. Press Save.
16. After selecting N2 in Step 6, press Save.
17. Press the back arrow to return to the previous screen.
18. Press N2 Address.
19. Enter the N2 address through the keypad.
25TEC3000 Series On/Off or Floating Fan Coil Thermostats Installation Guide

Other manuals for Johnson Controls TEC3000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls TEC3000 Series and is the answer not in the manual?

Johnson Controls TEC3000 Series Specifications

General IconGeneral
BrandJohnson Controls
ModelTEC3000 Series
CategoryThermostat
LanguageEnglish

Related product manuals