Table 8: Occupancy determination
Sequence of operation (highest to lowest priority) Status indicated
Manual
Occupancy
Mode
(OCCOVRD-
MODE)
1
Occupancy BI
(BI1‑S, BI2‑S)
1
2, 3
Temporary
Occupancy
2,3
Occupancy
Schedule (External
or Schedule)
(OCC‑CONFIG,
NET‑OCC)
4
Motion
Sensor
4
Effective
Occupancy
(EFF‑OCC)
Occupancy
Source
(OCCSOURCE‑S)
Occupied Occupied-
Override
Unoccupied
Unoccupied-
Override
Occ Override
Closed
1
Occupied
Open
1
Unoccupied
Occupancy BI
True
2
NOT Occupied Temp Occupancy Temp Occ
True
3
NOT Occupied
Temp Occupancy Temp Occ BI
True Occupied
False Standby
Occupancy
Sensor
Occupied
Disabled Occupied
Unoccupied Unoccupied
Standby
Standby
Occupancy
Schedule
True Occupied
False Unoccupied
Occupancy
Sensor
No Override
Not Configured
1
False
5
Not Set
5
Disabled Occupied Occupancy
Schedule
1 Not Configured means that neither BI1 Config nor BI2 Config is set to Occupancy BI. Open and Closed refer to the
current state of the BI when configured as Occupancy.
2 True is triggered by interacting with the screen during a scheduled unoccupied period. A value of True can only occur
when the schedule is not Occupied.
3 When triggered by a BI configured for Temp Occ, the input is ignored when the schedule is Occupied, the Manual
Occupancy Mode is not No Override, or an Occupancy BI is configured.
4 Built-in occupancy sensing (PIR) or EI configured for Motion NO or Motion NC.
5 Not Set occurs when no events are scheduled through the local scheduler, or the schedule source is set to Schedule and
the Schedule is writing Not Set as the schedule.
Selecting schedule source
Scheduling (for networked models)
About this task:
The TEC3000 Thermostat Controller can operate as a stand-alone unit with an internal schedule or
scheduled with an external schedule. The OCC-CONFIG object sets the method used for scheduling.
If the OCC-CONFIG is set to External, the NET-OCC object is used to control the unit externally.
If the OCC-CONFIG is set to Schedule, the internal schedule commands the LOCAL-OCC object,
which sets the Occupancy Schedule command.
Note: If you do not have a schedule in the Schedule object and you have the OCC-CONFIG set
to Schedule, you can control the unit with the LOCAL-OCC object externally; however, we do
not recommend this method. See Table 9 for scheduling information.
Once the Occupancy Schedule command is set, the effective occupancy is determined by
settings shown in the Occupancy Determination table. See Table 8.
35TEC3000 Series On/Off or Floating Fan Coil Thermostats Installation Guide

Other manuals for Johnson Controls TEC3000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls TEC3000 Series and is the answer not in the manual?

Johnson Controls TEC3000 Series Specifications

General IconGeneral
BrandJohnson Controls
ModelTEC3000 Series
CategoryThermostat
LanguageEnglish

Related product manuals